UNILIGHT LED PPI
Controllers, recorders & signal conditioning

Process & PID controllers
The CNi-AL series are temperature and process limit controllers intended for measurement and alarm tasks. A single universal input accepts thermocouples, RTDs, analogue voltage or analogue current signals, so the same instrument can monitor a temperature as well as pressure, flow or other process variables measured by a transmitter, and switch alarms when limits are exceeded.
The controller evaluates the input and operates two relay alarm outputs, which can be set up for high, low or band logic. Process inputs are fully scalable, so the reading can be shown in practically any engineering unit with a selectable decimal point. Alarm menus are simplified, and a manual reset function is provided. Configuration is done with the front panel buttons, and the measured value is shown on a 4-digit LED display.
Stated accuracy is ±0.5 °C for temperature and 0.03 % of reading for process signals. The current input covers 0 to 20 mA. Input impedance is 10 MΩ on the 100 mV range and 1 MΩ on the 1 V and 10 V ranges, and lead resistance of up to 100 Ω is permitted. A 24 V DC excitation output rated 25 mA can supply a transmitter; it is not available with the low-power option.
Both alarm outputs are SPDT form C relays rated 3 A at 250 V AC or 30 V DC with a resistive load. The standard power supply accepts 90 to 240 V AC ±10 % at 50 to 400 Hz or 110 to 300 V DC; the low-voltage version is supplied with 24 V AC or 12 to 36 V DC. Interfaces listed for the series include RS-232, RS-485, USB and Ethernet.
The controllers are made in three panel sizes, 1/8, 1/16 and 1/32 DIN, so they can be fitted into existing cut-outs. The 1/8 DIN unit is 48 mm high and 127 mm deep. Ambient operating temperature is 0 to 55 °C. The series carries CE, UKCA, UL and RoHS markings. Models are designated CNi8-AL, CNi16-AL and CNi32-AL, with the suffix -DC for the low-voltage supply.
Please indicate the panel size, input type, power supply and the alarm logic required, and we will specify the matching model.
CNi8-AL, CNi16-AL, CNi32-AL, CNi8-AL-DC, CNi16-AL-DC, CNi32-AL-DC
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.