UNILIGHT LED PPI
Controllers, recorders & signal conditioning

Recorders & data loggers
The DataVU 6-1 is a compact paperless recorder for reliable process monitoring and data recording. It replaces a chart recorder with a 5.7-inch TFT colour touchscreen that displays trends and current values, and stores the recorded data electronically in 1 GB of internal memory.
The recorder processes up to six analogue inputs and up to six digital inputs, and the number of channels can be extended via Modbus. Measured data is recorded, displayed as trends or values on the touchscreen and kept in internal memory. Input types are handled according to the standards listed for the device, including IEC 60584-1 and ASTM E230M-11 for thermocouples and IEC 751 for resistance thermometers.
The I/O configuration is selected when ordering: 0, 3 or 6 analogue inputs, 0, 6 or 12 digital inputs, 0 or 12 digital outputs and 0, 1 or 2 analogue outputs. One relay with a changeover contact is always provided. A math and logic module is available as an option.
Communication is provided through Ethernet with an integrated web server, USB and RS-232 or RS-485, using Modbus RTU and Modbus TCP; IPv4, TCP and UDP are supported on the network. The display has a resolution of 640 × 480 pixels and a resistive touch surface. As an option, recording can be made compliant with FDA 21 CFR Part 11.
The instrument is supplied for 110 to 240 V AC (+10/−15 %, 48 to 63 Hz) or 20 to 30 V DC. It is installed in a panel cut-out of 138+1.0 × 138+1.0 mm, with front dimensions of 144 × 144 mm and a mounting depth of 119 mm. The front is protected to IP65 and the rear to IP20, and the weight is at most 1.6 kg. UL is listed, and the device complies with DIN EN 61010-1, DIN EN 61326-1, DIN EN 60721-3 and DIN IEC 61554.
Order codes such as VU610010001 or VU611011000 define the configuration. Typical applications are process monitoring, batch recording and control, and industrial data logging. Please tell us the number and type of inputs and outputs, the supply voltage and whether FDA 21 CFR Part 11 compliance is required.
VU610010001, VU611011000, VU611010000, VU611011100, VU611000000
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.