DwyerOmega DRSL-TEMP
DwyerOmega

DRSL-TEMP DIN rail loop-powered temperature signal conditioner

Signal conditioners & barriers

Manufacturer
DwyerOmega
Model
DRSL-TEMP
Instrument type
Signal conditioners & barriers
Inputs
type J or K thermocouple; 2-, 3- or 4-wire Pt100 RTD
Output
passive 4–20 mA or 0–20 mA
Accuracy
±0.05 %
Response time
selectable < 30 ms or 300 ms
Supply
loop-powered, 5.5 to 35 V DC (voltage loss 5.5 V DC)
Power consumption
0.7 W
Isolation
2-way, 300 V AC; test voltage 2.5 kV AC
EMC immunity
NAMUR NE 21, criterion A
Configuration
DIP switches
Mounting
35 mm DIN rail, EN 60715, no air gap required
Operating temperature
−25 to 70 °C
Protection
IP20
Dimensions (H × L × W)
113 × 115 × 6.1 mm
Weight
70 g
Approvals
CE, UL, RoHS
Request a quote
Review enquiry

The DRSL-TEMP is an isolated, DIN rail-mounted, loop-powered temperature signal conditioner for industrial process environments. It accepts type J or K thermocouples and 2-, 3- or 4-wire Pt100 RTD sensors and converts their signals into a standard current output for SCADA systems and PLC equipment.

The unit is powered by the host's output current loop and needs no separate power supply. It operates on 5.5 to 35 V DC, with a voltage loss of 5.5 V DC and a power consumption of 0.7 W. The output is a passive analogue current signal of 4–20 mA or 0–20 mA. Input and output are separated by two-way isolation rated 300 V AC, tested at 2.5 kV AC. Measurement ranges are configured with DIP switches.

Stated accuracy is ±0.05 %. The response time is selectable: fast, below 30 ms, or dampened, at 300 ms. Surge suppression and protection against transients are built in, and EMC immunity meets NAMUR NE 21, criterion A, which makes the conditioner suitable for electrically noisy environments. Pollution degree 2 and measurement/overvoltage category II apply.

The housing is a slimline 6 mm (6.1 mm) design, 113 mm high and 115 mm long, weighing 70 g. It mounts directly on a standard 35 mm DIN rail according to EN 60715 and can be installed without an air gap between modules. The protection degree is IP20. The unit operates from −25 to 70 °C and from 0 to 95 % RH non-condensing, and can be stored from −40 to 85 °C.

The conditioner carries CE, UL and RoHS markings and complies with UL 61010-1, EN 61010-1, EN 61326-1 and EN 61140. Ordering options cover the input type (J or K thermocouple or Pt100), the output range (4–20 mA or 0–20 mA) and the response time. Accessories include the RAIL-35-1 35 mm DIN rail and the DRSL-MOD-STOP module stop.

Typical applications are industrial process temperature monitoring and the interfacing of temperature sensors to SCADA systems and PLC equipment. Please send the sensor type, the required temperature range and the output signal with your enquiry.

Part numbers · 4

DRSL-TEMP-Sig-Cond, DRSL-TEMP, RAIL-35-1, DRSL-MOD-STOP

Industry applications

Selection notes

List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.