UNILIGHT LED PPI
Controllers, recorders & signal conditioning

I/O modules
The OME-DB-24C-series is a 24-channel open-collector output daughter board for industrial control systems. It is connected to a host controller or data acquisition card and provides 24 isolated open-collector transistor outputs for discrete signal switching.
Each output is an NPN open-collector transistor. When a channel is switched on by the host, the transistor connects the load to the common, and the load is supplied from an external voltage. The maximum load voltage is 35 V DC. The board requires an external source of 5 to 24 V DC at 100 mA, and its own power consumption is 0.4 A at +5 V.
Optical isolation of 3750 V DC separates the output channels from the host system. The isolation rating applies between the channels and the host side.
The board provides three connectors: one 50-pin connector, one 37-pin D-Sub connector and one 20-pin connector. A 1.5 m 50-pin flat cable is available for connection to the host. The board measures 220 × 130 mm. Permitted operating temperature is 0 to 60 °C, storage temperature −20 to 70 °C, and relative humidity 5 to 90 %, non-condensing.
The 24 outputs are accessed via the 50-pin, 37-pin D-Sub and 20-pin connectors described above. Two variants are offered: the standard OME-DB-24C for panel mounting and insertion into a compatible chassis slot, and the OME-DB-24C/DIN for installation in a DIN rail enclosure. The boards carry the CE mark and are RoHS compliant; the manufacturing reference is ISO 9001.
Applications named are programmable relay systems, industrial control environments, discrete signal switching and status monitoring via a host controller. Please state the mounting variant, the host card to which the board will be connected and whether the flat cable is needed in your enquiry.
OME-DB-24C, OME-DB-24C/DIN
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.