UNILIGHT LED PPI
Controllers, recorders & signal conditioning

Signal conditioners & barriers
TAS-331DG is a compact AC transducer that measures active or reactive power on single-phase or three-phase networks and converts it into a DC current or voltage signal proportional to the measured value. The output goes to a PLC, a controller, a panel indicator, an alarm unit or a data acquisition system, which makes the transducer a standard building block in generator and switchboard panels.
The device is microcontroller-based and has no potentiometers or other mechanical adjustment parts, which gives very good long-term calibration stability. Measurement accuracy is class 0.5 according to IEC 60688 over an ambient temperature range from −10 to 55 °C. Measuring current inputs of 0.75, 1.5, 3 or 6 A cover direct connection or current transformers, with a measuring range up to 200 % of nominal current. Measuring voltages range from 73 to 400 V phase to neutral, or up to 690 V between phases, and the frequency range is 20 to 80 Hz, so the transducer also works on generator sets running at variable speed.
The output characteristic can have up to three slopes. This gives higher resolution in the most important part of the range, for example around the nominal load of a generator, while still covering reverse power or overload. Typical response time is 100 to 225 ms. On power-up the transducer checks the wiring and indicates connection faults with an LED, which shortens commissioning.
Transducers are delivered either configured to the customer's data or unconfigured; in the second case they are set up with a free PC configuration tool and a connection cable kit. Auxiliary supply versions cover 57.7 to 690 V AC and 24 to 220 V DC. The case is IP40, the terminals IP20; the unit mounts on a 35 mm DIN rail or with two screws. It withstands high overload on the current inputs: four times nominal continuously, twenty times for 10 seconds and forty times for 1 second.
The product is designed for marine and offshore use and holds DNV and Lloyd's Register approvals, with vibration, shock and humidity tests to IEC 60068. Typical applications are generator control and load sharing, power management on ships and in power plants, grid connection and synchronising panels, hybrid and microgrid systems with solar and storage. Please state network type, nominal values and output signal when requesting a quotation.
2962010200.01, 2962010200.02, 2962010200.03, 2962010200.04, 2961860010.03, 2961860010.04
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.