UNILIGHT LED PPI
Controllers, recorders & signal conditioning

I/O modules
The Z-5DI-2DO is a multifunctional digital I/O module for data acquisition and automation systems. It combines five digital inputs and two relay outputs in one DIN rail housing and communicates with the Modbus RTU slave protocol, so digital field signals can be read and loads switched over a serial bus. It is listed for water and wastewater treatment, data acquisition, environmental monitoring, automation and production control, chemical and pharmaceutical plants, laboratories and testing, and remote monitoring and management.
The module acquires the digital input signals and converts them into digital data available in Modbus registers. The five inputs accept reed contacts, proximity switches, PNP and NPN sensors and dry contacts. Each input can also be used as a counter: five 32-bit totalisers count pulses up to a maximum frequency of 5 kHz, and their values are kept in non-volatile FeRAM memory, so counts are retained when the supply is switched off.
The two outputs are SPST relays rated 5 A at 250 V AC. The module works in two operating modes. As a slave I/O, the inputs are read and the relays switched by a master over the bus. In timed control logic mode, the module itself operates the outputs according to configured timing functions.
Communication is via RS485 or USB with the Modbus RTU protocol. Configuration is carried out with the setup software. Isolation is 1.5 kV AC between the inputs and the other circuits and 3.75 kV AC between the outputs and the other circuits. The module is powered with 10–40 V DC or 19–28 V AC.
The module mounts quickly on a DIN 46277 rail according to IEC EN 60715. For installation, the rail bus accessories Z-PC-DINAL2-17.5, Z-PC-DIN2-17.5 and Z-PC-DIN8-17.5 are listed as mandatory accessories, which provide the connection to the rail bus. Optional accessories are K107USB, S107USB and S117P1. The module complies with RoHS and REACH and is covered by an EU Declaration of Conformity.
Please state the number of modules, the type of input signals and the accessories required in your enquiry.
Z-5DI-2DO
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.