The AFG series is a duct-mounted averaging flow grid for sensing velocity pressure in ducts carrying air or compatible gases. It does not display a value itself; it supplies a continuous differential pressure signal to an external instrument such as a manometer or a differential pressure transducer, from which air velocity and volume flow rate are determined.
The grid consists of two tubes. In square or rectangular ducts they are mounted diagonally across the duct, and in round ducts they are mounted diametrically. One tube senses total pressure, while the other senses static pressure at an angle. Because the pressures are averaged along the length of the tubes, the resulting differential is representative of the whole cross-section and is proportional to the velocity pressure.
The grid covers air velocities from 295.2 to 5904 FPM with an accuracy of ±5 %. It can be trimmed to length and fits ducts up to 60.4 in diagonal or 59.4 in diameter. The maximum operating temperature is 176 °F. Pressure connections are 5/16 in barbed fittings.
Wetted materials are 304 stainless steel, PVC, polyurethane, acetal plastics and neoprene rubber. Two models are available: AFG-1 with 5/16 in (8 mm) tubes of 27 in (688 mm) length, and AFG-2 with 5/8 in (16 mm) tubes of 59-4/5 in (1518 mm) length. RoHS conformity (RoHS 2015/863) is stated.
Each unit is supplied as a complete kit with two probes and the installation hardware: adapters, duct caps, drilling templates and self-tapping screws. The device is not field serviceable and must be returned for repair.
Applications named for the flow grid are HVAC zone control, retrofit air flow measurement, display of differential pressure or volume flow, flow rate alarm systems and integration into control systems. To select the right model, please send the duct shape and dimensions, the expected air velocity range and the instrument to which the signal will be connected.
AFG-1, AFG-2
State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.