EDT 96
Pressure

Pressure transmitters
The APC-2000ALW is a smart pressure transmitter with an analogue current output and HART protocol. It is used for pressure measurement and belongs to a family of instruments that also covers differential pressure measurement and hydrostatic level measurement.
The transmitter measures pressure and provides a standard current signal together with digital HART communication. The output can be configured as 4–20 mA, 0–20 mA or 0–5 mA. A backlit display shows the measured value, and the panel keys allow local programming of the measuring range, zero shift, output characteristic and damping ratio.
The standard accuracy is 0.075 %, with 0.05 % available on request. The diaphragm is gold-plated (Au). Housings are available in aluminium or stainless steel.
The transmitter holds a SIL 2 certificate for use in safety-related loops. It is certified for intrinsic safety and explosion-proof design under ATEX, IECEx, FM and INMETRO, holds marine certificates from DNV and BV, and has an MID certificate according to directive 2004/22/EC and OIML recommendation R140:2007.
The APC-2000ALM is the corresponding version with Modbus RTU protocol and galvanic isolation of the power supply and communication bus. Related transmitters include the PCE-28.SMART and PCE-28.SMART/EXD with 4–20 mA and HART; the PCE-28 and PCE-28/EXD with any range from 0–25 mbar to 0–1000 bar and 4–20 mA two-wire or 0–10 V output; the PCE-28.Modbus with Modbus RTU; the low-voltage PC-29A and PC-29B; the AS with zero and span potentiometers, 0.4 % accuracy, ranges from 0–1 to 0–25 and process connections 1/2" NPT M, G1/2", M20 × 1.5, RG or RM; and the APCE-2000PD with HART and a rangeability of 100:1.
Typical applications named for the series are pressure, differential pressure and hydrostatic level measurement.
When enquiring, please state the measuring range, pressure type, process connection, output signal, housing material and required certificates (Ex, SIL, marine or MID).
APC-2000ALW, APC-2000ALM, PCE-28.SMART, PCE-28.SMART/EXD, PCE-28, PCE-28/EXD, PCE-28.Modbus, PC-29A, PC-29B, AS, APCE-2000PD
Specify whether the reference is gauge, absolute or differential pressure. Include the normal span and the largest pressure the instrument may see.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.