Controllers, recorders & signal conditioning

Process & PID controllers
The AR18 Series is a digital controller in DIN 96 × 96 format for industrial control of temperature, humidity and other physical quantities. It is available as a one-setting two-position controller, a two-setting two-position controller and a three-position controller, and its operation is designed to be simple, using only the front keys.
The controller accepts thermocouples B, R, S, K, E, J, T, N, PLII, C (WRe5-26), U and L (DIN 43710) and metal-chromel (AuFe-Cr), Pt100 and JPt100 3-wire RTDs, mV and V DC signals and 0–20 or 4–20 mA, selected by measuring range code. It processes the signal every 0.25 s and switches the control outputs according to set points, hysteresis or dead band. Display accuracy is ±(0.25 % FS + 1 digit) at 23 ±5 °C, and the measured value can be displayed from −10 to 110 % of range.
The measured value appears on a red 4-digit LED display 14.3 mm high, settings on a green 4-digit display, and alarm limits, hysteresis and dead band on an orange 2-digit display. Control outputs 1 and 2 are either relay contacts (1c, 240 VAC, 5 A resistive, 2 A inductive) or SSR drive voltage (12 VDC, max. 30 mA). Options are high and low limit alarm outputs (contact 1a, 240 VAC 2 A, fixed hysteresis 0.2 % FS) and an analogue retransmission output of the measured value as 4–20 mA, 0–10 V or 0–10 mV, accurate to ±0.3 % FS with approximately 1/13,000 resolution. Settings are stored in EEPROM.
The unit runs on 100–240 VAC ±10 % at 50/60 Hz and consumes up to 14 VA. Noise rejection is at least 50 dB in normal mode and 130 dB in common mode. It is push-in panel mounted in a 92 × 92 mm cut-out for panels 1.0 to 4.0 mm thick, measures 96 × 96 × 120 mm with 100 mm behind the panel and weighs approximately 340 g. The front is dust- and drip-proof, equivalent to IP66. Operating conditions are −10 to 50 °C, up to 90 % RH and 2000 m, overvoltage category II and pollution degree 2. The controller supports the RoHS directive, and materials meet UL94V-0. A terminal cover, QCR003, is available separately.
Please state the input type and range, control mode, output types and required options when enquiring.
AR18F-1DE, QCR003
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.