UNILIGHT LED PPI
Controllers, recorders & signal conditioning

I/O modules
CIO 116 is a CAN bus-based input module that adds 16 digital inputs to a compatible genset or power management controller. It is used in complex installations where the controller's own inputs are not sufficient, and connects to the controller over the CAN bus.
The sixteen inputs are arranged in two groups of eight, each configurable for positive or negative common, so the module can be used with both sourcing and sinking contacts. An input is detected as ON between ±8 V and ±36 V DC and as OFF below 2 V DC; input impedance is 4.7 kΩ. Galvanic separation of 600 V at 50 Hz for one minute protects the bus and electronics from disturbances in the field wiring.
The module is supplied with 12 or 24 V DC and operates over a wide voltage range from 6 to 36 V DC. Power consumption is at most 0.5 W. A solid-state status output, rated up to 30 V AC or DC and 1 A up to 40 °C or 0.8 A up to 70 °C, signals the module state to external equipment. LEDs show the module status and the state of every input, which simplifies commissioning and troubleshooting.
Communication with the host controller runs over the CAN bus. The module is mounted on a 35 mm DIN rail, has IP20 protection and operates from −40 to +70 °C at altitudes up to 4000 m. It carries CE marking and cULus listing.
Typical applications are generator and engine control, power and energy management systems, modular control with an optional PLC, grid connection with or without synchronisation, hybrid and microgrid systems, off-grid power and combined solar, storage, genset and mains installations. Please tell us which controller the module will be connected to, so that compatibility can be confirmed with your quotation.
2912890240
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.