The ComEx Global Ex i illuminated indicator module is an explosion-protected device for visualising machine and system states with coloured LED light in potentially explosive atmospheres. It is certified for use in Zone 1 and Zone 21 and is used in oil and gas, chemical and pharmaceutical plants, the energy sector including hydrogen and LNG, manufacturing and logistics, and food and beverage production.
The module operates on 12–30 VDC with a rated insulation voltage of 30 V. It combines the types of protection flameproof enclosure and intrinsic safety and is marked Ex db ia IIC Gb and Ex db ia I Mb; for North America it is marked Class I, Zone 1, AEx db ia IIC Gb and Class I, Division 2, Groups A, B, C, D. The LED is available in five colours – red, green, yellow, white and blue – so that different states can be distinguished at a glance.
Two mounting versions are offered. The panel-mounted version (07-3354-44*) is locked by bayonet catch to the signal device actuators 07-3400-L*; it measures 72 × 50.3 × 33.3 mm and weighs approximately 110 g. The rail-mounted version (07-3352-14*) latches onto an NS 35 × 7.5 mounting rail; it measures 93.6 × 58 × 38 mm and weighs approximately 90 g. Connection is by screw terminals for conductors of 0.75 to 2.5 mm² (18 to 12 AWG).
The enclosure is thermoplastic with IP20 protection to EN 60529. The service temperature range is −55 to +85 °C. Electrical and mechanical life are each specified at more than 10⁵ running hours.
The module conforms to EN IEC 60079-0, EN 60079-1, EN IEC 60079-7 and EN 60079-11, to the EMC standards EN 61000-6-2 and EN 61000-6-4 and to EN IEC 63000. Approvals include ATEX, UKEX, IECEx, UL, EAC and PESO, together with CE marking. Installation and inspection follow IEC 60079-14 and IEC 60079-17.
Article numbers depend on the mounting version and LED colour, for example 07-3352-7D0004.
Please state the LED colour, mounting version, quantity and required approval when enquiring.
07-3352-14*, 07-3354-44*, 07-3352-7D0004
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.