Surent G480
Flow

Differential pressure flow elements
The FPT-3000 series are economical averaging pitot tube flow sensors for flow rate measurement of compatible gases, liquids and steam. They are inserted into the pipeline through a compression fitting and, together with a suitable differential pressure gauge, form a complete flow-indicating system.
The sensor uses two averaging pitot tubes. One faces the flow and senses the total pressure at several points across the pipe; the other senses the static pressure. The difference between the two is related to the flow velocity, and because the pressures are averaged across the diameter, there is no need to traverse the flowing stream with a single-point pitot tube. The design produces a low pressure drop.
Accuracy is ±2 %. The sensors are rated for a maximum pressure of 200 psi and temperatures from 0 to 93.3 °C. Versions are available for pipe sizes of 1″, 1-1/4″, 1-1/2″, 2″, 2-1/2″, 3″, 4″, 6″, 8″ and 10″, and matching differential pressure gauges cover ranges from 2 to 100 in w.c.
The head and sensor tube are made of 304 stainless steel, a rugged construction that gives a stable, non-clogging design with low maintenance. Both pressure connections are fitted with shut-off valves made of brass with TFE seats and Buna-N O-rings, so the gauge can be connected or removed without shutting down the line. Pressure connections are 1/4″ NPT male, with 1/8″ female NPT. The sensor is RoHS compliant and is supplied complete with the shut-off valves, a compression fitting for mounting and an operator's manual.
Typical applications are monitoring of natural gas, flare, flue and stack gas; boiler feed-water and cooling water systems; superheated, saturated or geothermal steam lines; combustion air and compressed air circuits; oil flow measurement; and remediation projects.
To select the right sensor, please send the pipe size, medium, expected flow range, pressure and temperature, and whether a matching differential pressure gauge is required.
FPT-3010, FPT-3012, FPT-3015, FPT-3020, FPT-3025, FPT-3030, FPT-3040, FPT-3060, FPT-3080, FPT-3100
State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.