Surent G480
Flow

Flow switches & indicators
The FSW-6000 and FSW-7000 series are thermal dispersion flow switches for monitoring the flow status of liquids, air and gas. They can also be used to detect liquid level in tanks and pipes. Having no moving parts, the switches are designed for maintenance-free operation.
The sensor contains two platinum resistance temperature detectors. One measures the temperature of the medium, the other is heated above it. Flowing medium carries heat away from the heated element; the higher the flow, the smaller the temperature difference between the two RTDs. When the difference corresponds to the set point, the switch changes state. Because the reference RTD follows the medium temperature, the temperature compensation is not affected by temperature gradients.
The switch covers gas velocities from 0.16 to 49 ft/s and liquid velocities from 0.09 to 9.84 ft/s in pipes from 1 to 4 in. Accuracy is ±10 % and repeatability ±1 %. The response time is adjustable from 1 to 10 seconds. The sensor withstands a working pressure of up to 300 bar (4351 psi), process temperatures from −20 to 80 °C and ambient temperatures from −20 to 60 °C.
An integrated 8-LED bargraph shows the relative flow rate and the set point status, which simplifies adjustment on site. The output is an SPDT relay rated 5 A at 250 V AC. The FSW-6000 is powered from 85–240 V AC and the FSW-7000 from 24 V DC. The standard cable length is 6.5 ft, and the enclosure is rated IP65 / NEMA 4. The switches are CE marked and RoHS compliant.
Housings are available in glass-filled nylon or die-cast aluminium; the aluminium enclosure is intended for hazardous environments. Wetted parts are 316 stainless steel, with ECTFE or epoxy coatings for aggressive media. Process connections include 1/2″ to 1-1/2″ NPT, Tri-Grip sanitary connections for applications with CIP cleaning, and flanges; standard insertion lengths are 35, 50 and 75 mm. Installation on the side of a horizontal pipe or in a vertical pipe with upward flow is recommended.
Please state the medium, pipe size, flow range, process connection and supply voltage when you request a quotation.
FSW-6212, FSW-7111, FSW-7112, 70A-1, TX4-100, U24Y175, FSW-6(*)(**)(***), FSW-7(*)(**)(***)
State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.