DwyerOmega HE559 SmartStix
DwyerOmega

HE559 SmartStix compact I/O expansion modules for CsCAN network

I/O modules

Manufacturer
DwyerOmega
Model
HE559 SmartStix
Instrument type
I/O modules
Network
CsCAN (control station area network)
Nodes
up to 253
Distance
457 m per segment; 1829 m with repeaters
Digital inputs
16 or 32 DC inputs (HE559DIM)
Digital outputs
16 or 32 DC outputs; 16 relay outputs
Analogue I/O
4 inputs and 2 outputs; ±5 V, ±10 V, 4–20 mA, ±20 mA
Analogue resolution / accuracy
14-bit; 0.1 % at 25 °C
Response
digital input ≤ 3 ms; analogue output 2 ms; relay 10 ms on / 12 ms off
Isolation
analogue 1000 V DC / 300 V RMS; digital photo coupler
Protection
electronic short-circuit protection (ESCP)
Module ID
two rotary switches
Connection
removable screw terminals; 5-pin network connector
Mounting
DIN rail
Dimensions
115 × 48 × 50 mm (16 I/O); 176 × 48 × 50 mm (32 I/O, analogue, relay)
Approvals
CE, UL
Request a quote
Review enquiry

The HE559 SmartStix modules are compact, terminal-block style I/O expansion units for XE, XT and XL series operator control stations (OCS). They extend the analogue and digital I/O capacity of the controller over a CsCAN network and can be deployed locally next to the controller or remotely in the field.

The modules connect to any OCS that has a CsCAN network port. Up to 253 nodes can be connected in total. A network segment can be up to 457 m (1500 ft) long, and up to 1829 m (6000 ft) can be reached with repeaters. The module ID on the network is set with two rotary switches, and LEDs indicate the state of the I/O points, power, module status and network activity.

Several I/O versions are available: 16 or 32 DC inputs (HE559DIM models), 16 or 32 DC outputs, 16 relay outputs, and a mixed analogue module with four analogue inputs and two analogue outputs. Analogue ranges include ±5 V, ±10 V DC, 4–20 mA and ±20 mA, with 14-bit resolution and 0.1 % accuracy at 25 °C; the absolute maximum input voltage is ±10 V. Digital inputs respond in 3 ms or less, analogue outputs switch in 2 ms, and relay outputs in at most 10 ms (off to on) and 12 ms (on to off).

Analogue channels are isolated to 1000 V DC according to IEC 61010-1, or 300 V RMS, and digital channels are isolated by photo couplers. Outputs are protected by electronic short-circuit protection (ESCP), and digital and relay outputs are configurable.

The modules are extremely compact, with a height of only 50 mm and a depth of 48 mm. 16-point modules other than relay versions are 115 mm long, while 32-point, analogue and relay modules are 176 mm long. Wiring is made on removable screw terminals for easy field replacement, the modules mount on a DIN rail, and a 5-pin terminal-style network connector is included. CE and UL are listed.

Models include HE559DIM610, HE559DIM710, HE559DIQ816, HE559DQM602, HE559DQM606, HE559DQM706 and HE559MIX577. Applications named for the modules are industrial control systems, process automation and interfacing of sensors and actuators. Please send the controller model and the number and type of I/O points required with your enquiry.

Part numbers · 7

HE559DIM610, HE559DIM710, HE559DIQ816, HE559DQM602, HE559DQM606, HE559DQM706, HE559MIX577

Industry applications

Selection notes

List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.