EDT 96
Pressure

Differential pressure transmitters
IDPT is an industrial differential pressure transmitter for very low pressures of clean, dry gases. It is intended for critical applications where small pressure differences must be measured with stable accuracy, in semiconductor and pharmaceutical production, laboratories, fume hoods, high-purity and HVAC pressure applications. This version covers 0 to 0.5 inches of water column.
Two sensing technologies are used, depending on the range. For the lowest ranges from 0–0.25 to 0–1 inH₂O, a capacitive pressure sensor is fitted; for ranges from 0–2.5 to 0–10 inH₂O, a piezo sensor. Standard accuracy is ±0.5 % of full scale, with ±0.25 % available as an option, and long-term stability is ±0.5 % of full scale per year. Temperature effects are compensated between 2 and 57 °C, and the transmitter operates from −20 to 70 °C.
The output is selected in the field. As a two-wire loop-powered device the transmitter delivers 4–20 mA with a loop resistance of up to 1045 Ω; as a three-wire device it provides a 0–5 V or 0–10 V signal into a minimum load of 1 kΩ. Push buttons allow zero and span to be adjusted on site without external equipment, which simplifies commissioning and periodic checks. Wiring is made on screw terminals.
Pressure is connected through barbed stainless steel fittings for 3/16 inch ID tubing. The transmitter is not position sensitive, so it can be mounted in any orientation on a wall or in a panel. The housing is water-resistant and rated IP11 / NEMA Type 2. The device is CE marked.
The series is available in ranges of 0.25, 0.5, 1, 2.5, 5 and 10 inH₂O, with two accuracy grades and in two-wire or three-wire versions. When requesting a quotation, please confirm the range, accuracy grade and output you need; if the application involves humid or contaminated gas, please describe the medium so that a suitable solution can be proposed.
IDPT-23U-IN
Specify whether the reference is gauge, absolute or differential pressure. Include the normal span and the largest pressure the instrument may see.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.