Type 8805
Control valves & actuators

Valve actuators
LIN-E-AIRE actuators are pneumatic spring-and-diaphragm actuators for the automatic operation of control valves. A varying air pressure from an external control device acts on the diaphragm and moves the push rod, which opens, closes or throttles the valve plug. The actuators are used with Hi-Flow globe valves, sanitary globe valves and butterfly valves of other brands, including valves for steam.
Two types determine the behaviour on loss of air. In the air-to-lower type, the push rod moves up when the air supply fails; in the air-to-raise type, it moves down. The choice therefore defines whether the valve opens or closes in a failure situation, which is selected according to the process.
The actuators are built with effective diaphragm areas of 20, 45 or 80 in² and maximum strokes from 1 in to 2-1/4 in (25.4 to 57.2 mm). The standard operating pressure range is 3 to 15 psi (20 to 100 kPa); with option Z, special ranges of 2–10 psi or 10–18 psi are available. Depending on the size, the maximum air supply pressure is 50 to 100 psig (350 to 700 kPa). Air connections are 1/4 in NPT female, and the maximum temperature is 150 °F.
The frame is cast iron with a baked enamel finish, the diaphragm is nylon-reinforced Buna-N rubber, and springs and fittings are plated spring steel and plated steel. Matching valve bodies are offered in ductile iron, bronze and 316 stainless steel with 1/2″ to 2″ NPT or 1-1/2″ to 4″ flanged connections. Low range flanges are Class 125 iron or Class 150 bronze, high range flanges Class 250 iron or Class 300 bronze, and reduced port options L0 and L1 are available.
For precise positioning, the actuator can be combined with a positioner, catalogue number 100N or 165. Actuator and valve can be supplied as a factory-matched assembly, or the actuator can be mounted on the valve body in the field.
Please send the valve type and size, the required fail-safe action, the control signal range and the available air supply pressure with your enquiry.
15S620, 15S621, 15S622, 15S623, 15S630, 15S631, 15S633, 15S640, 15S641, 15S642, 15S643, 15S644, 15S650, 15S651, 15S652, 15S653, 15S654
Record the valve tag, travel, pressure drop and actuator supply. Specify the required fail position and the existing feedback interface.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.