Gems Sensors & Controls LS-700
Gems Sensors & Controls

LS-700 compact multi-point float level switch

Float & magnetic level indicators

Manufacturer
Gems Sensors & Controls
Model
LS-700
Instrument type
Float & magnetic level indicators
Sensor type
Multi-point float level switch with reed switches
Actuation levels
1 to 5
Length overall
Up to 48" (1219 mm)
Stem and mounting material
Brass or stainless steel (316 SS)
Max. operating pressure
1000 psi
Operating temperature
−40 to 450 °F (−40 to 232 °C)
Minimum specific gravity
0.45 to 1.10, by float
Switch
SPST, N.O. or N.C., 20 VA or 100 VA
Lead wires
22 AWG, 24", PTFE
Mountings
1/8", 3/4", 1", 1-1/4" NPT; 1-5/16-12UNF-2A; 3/8-24; 3-5/8" flange; sanitary on request
Electrical options
Integral receptacle (2–5 pin), 1/2" MNPT conduit adapter
Enclosure
NEMA 4 versions
Approvals
UL Recognized (File E45168), CSA Listed versions
Request a quote
Review enquiry

The LS-700 series is a compact multi-point float level switch for restricted spaces, including tanks less than 4 feet high. It combines the rugged durability of stainless steel or brass construction with a lightweight package and is intended for OEM and industrial applications.

The switch works with floats that move along a stem. Each float carries a magnet that actuates a reed switch inside the stem when the liquid level reaches the corresponding point. One to five actuation levels can be provided on a single unit. The switches are SPST, normally open or normally closed, rated 20 VA or 100 VA. The manufacturer notes that very low currents (below about 5 mA) can prevent the contacts of a standard 20 VA reed switch from cleaning themselves or provide too little energy.

Overall lengths up to 48 inches (1219 mm) are available. The maximum operating pressure is 1000 psi, and the operating temperature range is −40 °F to 450 °F (−40 °C to 232 °C), with high-temperature versions offered. Depending on the float, liquids with a minimum specific gravity from 0.45 to 1.10 can be detected.

Stems and mountings are made of brass or stainless steel, including 316 stainless steel. Mounting threads and flanges include 1/8", 3/4", 1" and 1-1/4" NPT, 1-5/16-12UNF-2A and 3/8-24 threads and a 3-5/8" diameter flange; sanitary flange mountings are available on request. Lead wires are 22 AWG PTFE, 24 inches long; an integral receptacle with 2 to 5 pins and a 1/2" MNPT conduit adapter are offered, and NEMA 4 versions exist.

Further options include a bent stem version (LS-77700), integrated temperature sensing with transducers or thermostats, and solid-state relays. UL Recognized versions (File No. E45168) and CSA Listed versions are available. A large number of configured part numbers is listed for the series.

Typical applications named for the LS-700 are OEM equipment, industrial applications, restricted spaces and tanks less than 4 feet high.

When enquiring, please provide the number and positions of the switch points, the switching function, the liquid and its specific gravity, the pressure and temperature, the mounting and material, or the existing part number.

Part numbers · 25

W1100171, W1070233, W1072228, W1087034, W1098178, W179891, W69159, W1101077, 010-1652, W1109962, W1086111, W1114499, W1101316, W1045796, 016-4057, W1114938, W1113353, W1100064, W1115353, W1090334, W1119098, W991709, W1077895, W1046171, W1098069

Industry applications

Selection notes

Identify the vessel height, nozzle position and surface conditions. A point alarm and a continuous level reading require different outputs.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment