
UNILIGHT LED PPI
Controllers, recorders & signal conditioning

I/O modules
Type ME64 is a configurable input/output module for the local acquisition of sensor and control signals directly on the plant. It is designed for process automation, for example for collecting feedback signals and for decentralised control of process valves, and its housing rating of IP65, IP67 and IP69K makes it suitable for splash-proof environments.
Sensors and actuators are connected to the module through M12 A-coded connectors. The module transmits the signals over a CANopen-based internal bus to an Industrial Ethernet gateway (Type ME63), which provides the link to the higher-level control system. Power is fed in via an M12 L-coded port rated up to 32 A. Integrated diagnostics detect wire breaks and short circuits.
Three variants are listed. The 16DI module of the first generation (346856) has 16 digital inputs, four of them usable as frequency inputs; variant 2 (20021994) offers eight frequency inputs. The universal module (20098112) has channels that can be configured individually as analogue inputs, digital inputs or digital outputs. Sensor supply is 16 × 125 mA on the 16DI module and 250 mA per channel on the universal module.
On the universal module, analogue accuracy is ±0.5 % of final value, with input impedance of ≤ 110 Ω for current and ≥ 115 kΩ for voltage; digital outputs switch up to 1 A at a clock frequency up to 20 kHz. Digital input impedance is above 4 kΩ. Sampling time is adjustable from 1 ms to 4 s, or 0.25 Hz to 1 kHz for frequency inputs.
The module operates on 24 V DC (+20 %/−15 %) and consumes 4.12 W (16DI) or 4.8 W (universal). The housing is polycarbonate, measures 210 × 65 × 18 mm and weighs 400 g. Ambient temperature is −20 to +60 °C and storage temperature −30 to +80 °C. UL listing is optional; the module complies with EU directives and IEC 60529.
Configuration is carried out with the Communicator software (Type 8920).
With your enquiry, please state the required variant (16DI or universal), whether UL listing is needed, the gateway in use and the quantity.
346856, 20021994, 20098112
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.