The MRM57 is a module-type temperature controller of the MCM57-MRM57 series, designed for multi-loop temperature control in a compact, DIN-rail-mountable format. A system consists of an MCM57 communication (COM) module and one or more MRM57 temperature control modules. At only 22.6 mm wide, the modules can be mounted side by side without gaps.
Each MRM57 module handles two channels of input and output. Inputs convert temperature, humidity and other physical quantities: the multi-input version accepts thermocouples B, R, S, K, E, J, T, N, PLII, C (WRe5-26), U and L, Pt100 and JPt100 resistance thermometers and mV signals, while the volt-input version accepts ranges from ±1 V to 0–10 V. Control uses Expert PID with an auto-tuning function. The control modes are two independent loops (2 inputs, 2 outputs), one channel with heating and cooling or two heating or two cooling stages (1 input, 2 outputs), one channel cascade control (2 inputs, 1 output) and one channel PV switching control (2 inputs, 2 outputs).
Control outputs are available as transistor open collector (24 VDC, 100 mA), SSR drive voltage (12 VDC, 30 mA), current 4–20 mA (max. load 500 Ω) or voltage 0–10 V (max. 2 mA). Options include three digital inputs per channel (six in total) for no-voltage contacts, one analogue output per channel as 0–10 mV, 4–20 mA (max. 300 Ω) or 0–10 V, and a program function with four patterns of 32 steps.
The modules are connected by bus connectors; the COM module distributes power and communicates with a master unit such as a PLC or PC via RS-422 (MCM57-2) or RS-485 (MCM57-5), using Modbus RTU or the manufacturer's own protocol. Up to 31 units form one group and up to four groups can be connected to a master. Slave address, protocol, baud rate and data format are set with DIP switches.
Supply is 24 VDC ±10 % from an external source; hot-swapping is not supported. The module measures 108 × 22.6 × 113.6 mm and weighs approximately 150 g. It operates at −10 to 50 °C, up to 90 % RH without condensation and up to 2000 m. It is CE marked to EN 61326-1, complies with IEC 60664 and RoHS. Applications include temperature, humidity and multi-loop process control.
Please state the input type, control mode, output type, options and communication module when enquiring.
MCM57-E51-C, MCM57-2, MCM57-5, MCM57-0, MCM57-9, MRM57-8, MRM57-6, MRM57-C, MRM57-00, MRM57-03, MRM57-04, MRM57-06, MRM57-0, MRM57-1, MRM57-2, MRM57-3, MRM57-9, QCS003, MRM57-88P00
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.