Surent G480
Flow

Differential pressure flow elements
The PAFS-1000 series are averaging flow sensors for heating, ventilation and air conditioning. They are designed to sense the velocity pressure in the inlet section of variable air volume (VAV) terminal units and fan terminal units, and can also be installed at other locations in main and branch ducts. Combined with a differential pressure transmitter or a VAV controller, the sensor provides the signal from which the air flow is calculated.
The sensor has two sets of ports. The "H" port senses total pressure, facing the air flow, and the "L" port senses static pressure; the difference between the two is the velocity pressure, which is proportional to the square of the air velocity. Several sensing points distributed along the sensor average the pressure over the duct cross-section, which gives a more representative reading than a single point when the flow profile is not uniform.
Ten models are available, from PAFS-1002 to PAFS-1011, with 1 to 10 sensing points and sensor lengths from 8.02 to 60.72 cm. They accommodate duct and box sizes from 4 to 30 inches. A simple integral mounting flange with gasket fits both round and rectangular ducts.
The wetted parts are made of ABS and polycarbonate with a UL94-5V flammability rating. Pressure connections are push-on fittings for tubing with 1/4 in (6 mm) inside diameter and 3/8 in (10 mm) outside diameter. The operating temperature range is 4 to 49 °C. The sensor weighs about 28 g and is RoHS compliant.
Typical applications are air flow sensing in VAV terminal units, zone control in HVAC systems, differential pressure sensing in main and branch ducts, and retrofit air flow measurement in existing buildings. Please state the duct size or terminal unit inlet diameter so that the right model can be selected.
PAFS-1002, PAFS-1003, PAFS-1004, PAFS-1005, PAFS-1006, PAFS-1007, PAFS-1008, PAFS-1009, PAFS-1010, PAFS-1011
State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.