Surent G480
Flow

Vortex flowmeters
The RVL series is an inline vortex-shedding flow meter for liquids with a corrosion-resistant, all-plastic construction and no moving parts. It is designed for metering aggressive, easily contaminated, ultra-pure or corrosive liquids and slurries, where metal parts in contact with the fluid would be a source of contamination or corrosion.
The meter uses vortex-shedding technology. A bluff body in the flow path sheds vortices at a rate proportional to the flow velocity, and the meter converts this rate into a flow signal. Because there are no moving parts and no metal parts in contact with the liquid, the risk of fluid contamination associated with metal or moving parts is eliminated.
The RVL series covers line sizes from 6 to 76 mm (1/4 to 3 inches) and a flow range of 2.3 to 1,136 l/min (0.6 to 300 gpm), depending on size. Accuracy is ±1 %, repeatability ±0.25 % of actual flow, and the minimum response time to a step change in flow is 2 seconds. Fluid temperatures up to 95 °C are permitted.
The meter has a replaceable electronics module with a compact transmitter, available either as a two-wire 4–20 mA version or as a three-wire frequency pulse version. The pulse output uses a source–sink driver rated 1 A source and 1.5 A sink, with a typical output resistance of 10 Ω. Input power is 8–28 V DC. The electronics enclosure is corrosion resistant and rated NEMA 4X (IP66).
The meter body can be connected with butt fittings, NPT threads, or as a wafer mounted between flanges. The meter carries CE marking according to EN 50082-1:1992.
Options are the line size from 6 to 76 mm, the type of process connection and the signal output, 4–20 mA or frequency pulse. Media listed for the meter are ultra-pure water, highly corrosive chemicals and slurries, and the fields of use are wastewater treatment and industrial processes. Please state the liquid, line size, flow range, temperature and required output in your enquiry.
State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.