BARTEC SILAS
BARTEC

SILAS pressurisation control unit for Ex p enclosures

Process & PID controllers

Manufacturer
BARTEC
Model
SILAS
Instrument type
Process & PID controllers
Type of protection
Ex p, pressurised enclosure with leakage compensation (Ex pD / pzc)
Hazardous area
Zone 2 (Gc) or Zone 22 (Dc), explosion group II, category 3G/D
Ex marking
Ex ec nC [pzc] IIC T4/T6 Gc; Ex tc [pzc] IIIB T135 °C / T85 °C Dc
Pressure monitoring range
0 to 25 mbar
Pre-purge time
0 to 60 min, adjustable
Supply voltage
AC 230 V or AC 115 V, 50–60 Hz; DC 24 V
Power consumption
max. 8 W
Relays
purge valve control, Ex p enable (potential-free), status signal (potential-free)
Display and operation
single-line LCD, BCD selector, 3 buttons, 3 LEDs, bypass
Housing
fibreglass-reinforced polyester, min. IP54
Operating temperature
−20 to +60 °C (T4); −20 to +40 °C (T6)
Weight
1.2 kg
Request a quote
Review enquiry

SILAS is a compact automatic control unit for pressurised enclosures (type of protection Ex p) used in hazardous areas classified as Zone 2 for gas or Zone 22 for dust. It lets standard electrical equipment such as analysers, PLC panels, drives or PCs operate inside a cabinet placed in an explosive atmosphere: the cabinet is first flushed with protective gas and then kept at a small overpressure, so that the surrounding atmosphere cannot enter.

The unit runs the whole sequence on its own. During pre-purge it opens the purge valve and lets compressed air or inert gas flow through the enclosure for the set time, adjustable from 0 to 60 minutes according to the free volume of the cabinet. It then switches to operating mode, where the purge flow only compensates leakage and the internal pressure is monitored continuously in the range 0 to 25 mbar. Only after a successful purge and with correct pressure does the enable relay release power to the equipment inside; if pressure is lost, the relay drops and a separate potential-free status relay signals the fault to the control room.

Three relays are provided: one drives the purge valve, one is the potential-free Ex p enable contact, and one transmits status. Parameters are set with a BCD selector and three buttons and shown on a single-line LC display, with three LEDs for relay states and a bypass function for commissioning and service. The housing is fibreglass-reinforced polyester with at least IP54 protection; terminals accept fine-wire conductors from 0.08 to 2.5 mm². Supply versions for AC 230 V, AC 115 V and DC 24 V are available, power consumption is at most 8 W and the unit weighs 1.2 kg.

The system can be mounted outside or inside the protected enclosure, in versions for gas or dust applications, with or without a viewing window. Matching purge gas valves, pressure monitor, pressure reducer and an internal mounting kit complete the set; purge gas connections are G1/4" or G1/2". The controller carries ATEX and IECEx certificates and further national approvals and is marked Ex ec nC [pzc] IIC T4 or T6 Gc, Ex tc [pzc] IIIB T135 °C or T85 °C Dc.

Typical users are oil and gas facilities, chemical and pharmaceutical plants, hydrogen installations, power generation and food production, wherever standard equipment must stand in a classified area. Installation follows IEC/EN 60079-2 and IEC/EN 60079-14; periodic inspection to IEC/EN 60079-17 is recommended every three years. Please send the cabinet volume, area classification and supply voltage with your enquiry so that the right configuration can be selected.

Part numbers · 37

A7-3741-1110/.00, A7-3741-1110/00, A7-3741-1110/*00*, 05-0056-007*, 17-51P3-1604, 05-0056-008*, 05-0091-0275, A1-3741-7D0001, A7-3741-1a b 0/c d e f, A7-3741-1**0/****, A7-3741-1**0/1***, A7-3741-1**0/2***, A7-3741-1**0/4***, A1-3741-7C0001-F, A1-3741-610004, A1-3741-6B0001-B, A1-3741-6505, A1-3741-6B00002, A1-3741-6501, A1-3741-6502, A1-3741-6503ST, A1-3741-6505ST, A1-3741-6507ST, A1-3741-650001, A1-3741-650001BOM, A1-3741-650002BOM, A1-3741-6A0001, 05-2144-1211, A1-3741-610002, A1-3741-6D0004, A1-3741-6504, A1-3741-6506, A1-3741-6509, A1-3741-6501ST, A1-3741-6502ST, A1-3741-610003, A1-3741-6D0007

Industry applications

Selection notes

List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment

DEVICEEU