Honeywell Process Solutions SMARTLINK
Honeywell Process Solutions

SMARTLINK self-checking thermal mass flowmeter for natural gas and air

Thermal mass meters & flow controllers

Manufacturer
Honeywell Process Solutions
Model
SMARTLINK
Instrument type
Thermal mass meters & flow controllers
Measuring principle
thermal mass flow, constant temperature differential, two platinum RTDs
Media
natural gas, air
Turndown
50:1
Flow accuracy
±2 % of reading over 5–100 % of range (calibration stand); < ±2 % additional installed error
Temperature accuracy
±0.5 °C
Fluid temperature
−40 to +100 °C
Ambient temperature
−40 to +70 °C; LCD viewing −20 to +50 °C
Analogue outputs
2 isolated 4–20 mA (flow, ratio or temperature)
Relay outputs
3 fail-safe solid-state relay drives (test, alarm, limit)
Analogue input
1 × 4–20 mA from external meter for ratio calculation
Display
4-line × 20-character LCD with membrane keypad
Power supply
24 V DC; optional 115/230 V AC 50/60 Hz
Wetted materials
probe and screens 316 SS; flow body carbon steel
Enclosure
IP66, NEMA 4X, 12 and 13
Approvals
FM Class I Div 2, ATEX II 3 G/D, IECEx, UKCA, KC, CCC
Request a quote
Review enquiry

The SMARTLINK meter is a rugged, industrial, digital self-checking thermal mass flowmeter for monitoring the flow of natural gas and air. It provides precise, repeatable mass flow measurement, shows the instantaneous standard flow rate and the totalised flow, and has no moving parts. It is supplied with an in-line flow body.

The meter uses the constant temperature differential (ΔT) technique with two matched platinum RTD elements. One element measures the fluid temperature, while an intelligent bridge circuit heats the second element and keeps a constant temperature difference between the two. The power that must be delivered to the heated element to maintain this difference depends on the mass flow and is used to determine the flow rate.

Flow turndown is 50:1. On the calibration stand, accuracy is ±2 % of reading over 5 % to 100 % of the flow range (20:1 turndown), with less than ±2 % additional installed error. Advanced calibration extends the accuracy over a wider range of fluid temperatures. Temperature is measured with an accuracy of ±0.5 °C. The fluid temperature range is −40 to +100 °C and the ambient range −40 to +70 °C, with the LCD readable from −20 to +50 °C.

The meter has two isolated 4–20 mA outputs for flow, ratio or temperature, and three fail-safe solid-state relay drive outputs for test, alarm and limit functions, providing redundancy and alarm output for fail-safe operation. A 4–20 mA input accepts the signal of a second meter: when two meters are linked, the air/fuel ratio is monitored. A 4-line, 20-character LCD with membrane keypad is used for local display and operation. Power supply is 24 V DC, optionally 115/230 V AC.

The probe and screens are made of 316 stainless steel and the flow body of carbon steel. Conditioning screens in the flow body reduce straight-run piping requirements. The enclosure is rated IP66 and NEMA 4X, 12 and 13. The meter is FM-approved for Class I and II, Division 2, and Class I, Zone 2, Group IIC hazardous locations, and also carries ATEX II 3 G/D, IECEx, UKCA, KC and CCC approvals.

Natural gas models 0200, 0300, 0400 and 0600 are sized for 2, 3, 4 and 6 in lines, and air models 0800 to 2800 for 8 to 28 in lines. Typical applications are combustion air and gas flow measurement, air/fuel ratio monitoring, fuel usage tracking and emissions optimisation. Please send the medium, line size, flow range and supply voltage with your enquiry.

Part numbers · 10

0200 SLM, 0300 SLM, 0400 SLM, 0600 SLM, 0800 SLM, 1200 SLM, 1600 SLM, 2000 SLM, 2400 SLM, 2800 SLM

Industry applications

Selection notes

State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.