The VFS5 series are measuring transducers that convert sinusoidal frequency signals into standardised voltage or current output signals. The resulting analogue signal can be read by a controller, indicator or monitoring system. The devices are designed for harsh marine environments and for machine controllers and are approved by DNV, LR and BV.
The transducer accepts the sinusoidal frequency signal at its input and converts it linearly into a proportional output signal. The sensor input is galvanically isolated from the supply voltage. The measuring range can be fine-adjusted with a sealed integrated trimming potentiometer, and an integrated LED shows the operating status.
Input frequency ranges of 10–100 Hz, 20–1,000 Hz and 200–10,000 Hz are listed, and the upper range value can be customised. Examples are the VFS501-I2, with an input range of 20–1,000 Hz (upper value 100–1,000 Hz) and a 4–20 mA output, and the VFS502-G2, with an input range of 200–10,000 Hz (upper value 1,000–10,000 Hz) and a 2–10 V DC output. The output versions are 0–10 V DC (-G1), 2–10 V DC (-G2), 0–20 mA (-I1) and 4–20 mA (-I2); voltage outputs are short-circuit proof with a maximum load current of 20 mA.
The transducer is supplied with 9 to 32 V DC. It operates at ambient temperatures from −20 °C to +70 °C, can be stored from −45 °C to +85 °C and withstands humidity of up to 96 %. The compact housing allows side-by-side mounting on TS32 G-rails or TS35 top-hat rails; the body is flame-inhibiting and self-extinguishing (V0). Electrical connections are gold-plated A6.3 × 0.8 tab connectors to DIN 46244. The unit weighs 55 g.
The design is tested to IEC 60068 for vibration, shock and damp heat, to IEC 61000-4-2 to -4-6 and DIN EN 61000-6-2/-6-4 for EMC, to CISPR 16 for emission, to IEC 60553 and DIN EN 60529, and to DIN EN 50155 for railway electronics.
Listed fields of use are the shipbuilding industry, harsh environments and machine controllers.
Please state the input frequency range, the required output signal and the quantity when requesting a quotation.
VFS501-I2-352, VFS502-G2, VFS501-I2
List input types and the destination of each output. Match panel cutout, supply and communication options before choosing a replacement.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.