The AAL-2 is an insulation monitor for AC networks of the IT type, that is, isolated AC distribution systems in which no conductor is directly earthed. It supervises the insulation resistance between the network and the protective earth (PE) and warns as soon as the insulation deteriorates, before a second fault can cause a short circuit. The monitor can be used on single-phase and 3-phase networks up to 440 V AC.
The measuring principle is simple and continuous: the AAL-2 superimposes a 12 V DC measuring voltage on the network and measures the resulting current to earth. The insulation resistance is calculated from this current and shown on the analogue scale. If it drops below the set point, the built-in relay operates.
Two measuring ranges are available, 0 to 1 MΩ and 0 to 10 MΩ. The set point is adjustable from 0 to 150 kΩ in the 1 MΩ version and from 0 to 1.5 MΩ in the 10 MΩ version, and is indicated on the front. Response time is below 0.5 s in the 1 MΩ range and below 3.5 s in the 10 MΩ range. The monitor tolerates network leakage capacitances up to 25 µF or 250 µF respectively and works in networks with frequencies from 45 to 500 Hz. The input withstands 528 V AC continuously (440 V AC +20 %).
The relay can be ordered normally energised (NE) or normally de-energised (ND). A warning delay of 0 or 4 seconds and a power-up delay prevent false alarms from short transients. The auxiliary supply is 115, 230 or 400 V AC ±20 %.
The instrument is built for panel mounting in a 92 × 92 mm cutout and weighs about 0.45 kg. Protection is IP52, or IP54 with an optional gasket. It operates from −25 to 60 °C and is tested to IEC 60068 environmental standards and IACS UR E10, with insulation monitoring to IEC 61557-8 and UR recognition. Options include customised scale and design, a red point marker, a red scale section and anti-glare front glass.
Typical applications are marine and offshore: commercial vessels, offshore supply vessels, passenger ships and ferries, fishing vessels, harbour and inland vessels, pleasure boats, and offshore platforms and rigs. Please specify the measuring range, auxiliary supply, relay mode and warning delay in your enquiry.
4921230026D
Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.