3M Company b5005623006
3M Company

b5005623006 insulating plug capacitive voltage sensor for 25/28 kV deadbreak elbows

Current & voltage transducers

Manufacturer
3M Company
Model
b5005623006
Instrument type
Current & voltage transducers
Technology
capacitive voltage divider
Application
primary distribution grid
Voltage rating
up to 25/28 kV
Accuracy class
0.5
Frequency response
±1 % from 50 Hz to 3000 Hz
Compatibility
IEEE 386 deadbreak T-type separable connectors
Test point
integrated
Field calibration
not required
Standards
IEC 61869-1, IEC 61869-6, IEC 61869-11, IEEE 386, HD 629.1 S3
Request a quote
Review enquiry

This insulating plug voltage sensor, article b5005623006, is a high-accuracy voltage sensor for primary distribution grids. The sensing element is integrated into the basic insulating plug of a deadbreak T-type elbow, so voltage measurement is added at the cable connection itself rather than with a separate voltage transformer.

The sensor uses capacitive voltage divider technology. The divider produces a signal proportional to the primary voltage and provides real-time, accurate voltage measurement for smart grid applications. Compared with traditional voltage transformers, the sensor is smaller and lighter, and it does not require calibration in the field.

The sensor is rated for systems up to 25/28 kV. It meets accuracy class 0.5, and its frequency response is within ±1 % from 50 Hz to 3000 Hz. The sensor is listed as compact, high-accuracy and field calibration-free, and it is offered in separable T-type form compatible with IEEE 386 deadbreak connectors.

The capacitive design also provides a test point feature without compromising measurement accuracy, so the presence of voltage can be checked at the connector.

The plug is compatible with deadbreak T-type separable connectors to IEEE 386. Because it replaces a standard component of the separable connector, it is easy to integrate on site and suits both new installations and the retrofitting of existing systems. Relevant standards are IEC 61869-1, IEC 61869-6 and IEC 61869-11 for instrument transformers and low-power voltage sensors, IEEE 386 for separable insulated connectors and HD 629.1 S3 for cable accessories.

Applications named are smart grid applications and primary distribution grids, in new installations and in the retrofitting of existing systems. Please state the system voltage, the type of separable connector installed and the equipment to which the sensor signal will be connected in your enquiry.

Part numbers · 1

b5005623006

Industry applications

Selection notes

Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment