EDT 101
Temperature

Thermocouples
The CU and SCD series are explosion-proof thermocouple temperature sensors for hazardous locations. They are designed for places where flammable gases or vapours of flammable liquids are present and carry the explosion and ignition rating d2G4 under the Japanese explosion-protection guidelines for factory electrical equipment (gas and vapour).
Protection is provided by a pressure explosion-proof terminal box that withstands an internal pressure of 1 MPa gauge. Inside the box, minimum creepage distance and minimum insulation clearance are each 8 mm. The cable is brought in through a G1/2 conduit screw. The thermocouple element is installed in a protective tube that is connected to the terminal box and inserted into the process.
Five thermocouple types are available. Type R covers 0 to 800 °C with tolerance JIS Class 2. Type K covers −200 to 1200 °C. Type E covers −200 to 600 °C, type J 0 to 500 °C and type T −200 to 250 °C; for E, J and T, JIS Class 1 or Class 2 tolerance can be selected. Taken together, the series therefore spans measuring temperatures from −200 to 1200 °C, and the thermocouple type is chosen to suit the required range.
Protective tubes are available with outer diameters from 1.5 to 22 mm and in SUS304, SUS316, SUS310S, SUS347, NCF600 or Kanthal, so the tube material can be selected according to the temperature and the medium at the measuring point. For installation, straight, flange or nipple mounting can be chosen.
When ordering, the configuration is defined by the thermocouple type and tolerance class, the protective tube material and diameter, and the mounting style. These options allow the same explosion-proof terminal box design to be used across a range of measuring points in an installation with flammable gases or liquids.
To prepare a quotation, please send the thermocouple type and class, the required protective tube material, diameter and length, the mounting type and the number of sensors.
Match the sensing element, insertion length and wiring to the existing input. Separate the process temperature from the ambient temperature at the connection head.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.