Surent G480
Flow

Vortex flowmeters
CX8-M7C17D4E10N4 is a metal body vortex shedding flowmeter from the CP/CN/CT/CX series. It is designed to measure the flow of water, water/glycol mixtures and other low-viscosity liquids and combines the sensor, a rotatable LED display and a 4–20 mA output in one compact unit with a barbed process connection.
The liquid strikes a bluff body inside the meter, which sheds vortices alternately on each side. A piezoelectric sensor detects these vortices and generates a frequency proportional to the flow rate. The electronics convert this frequency into a 4–20 mA output signal and show the value on the LED display. There are no moving parts in the flow path.
Flow accuracy is ±2 % with ±0.25 % repeatability and a turndown of 10:1. The meter also measures the liquid temperature with an accuracy of ±2 °F. Response time is 450 ms, and the K-factor is 100 pulses per gallon. The permitted liquid viscosity is up to 15 cP. Operating temperature ranges from 35 to 210 °F (about 2 to 99 °C), and the proof pressure is up to 200 psi.
The meter is supplied with 10 to 30 V DC and draws 80 mA. The display has 3 or 4 digits and can be rotated to suit the installation. Wetted materials are brass, PEEK and FKM. The enclosure is rated IP65 and NEMA 4; the meter is CE marked and listed to ETL and CSA C22.4 No. 61010-1.
Within the series, a high-temperature version, a 2-wire intrinsically safe option, NPT, BSPT and BSPP process connections and pigtail or conduit box electrical connections are offered. For installation, a straight pipe run of 10 diameters upstream and 5 diameters downstream is required; the meter should be installed in horizontal, slightly ascending or vertical runs, with isolation ball valves for servicing.
Stated fields of use include mining, concrete batching, manufacturing, steel making, power generation, district heating, water treatment, pulp and paper and semiconductor production. Please send the liquid, flow range, temperature and preferred connection with your enquiry.
CX8-M7C17D4E10N4
State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.