DwyerOmega DA / DS
DwyerOmega

DA / DS Bourdon tube pressure switch with external set point adjustment

Pressure switches

Manufacturer
DwyerOmega
Model
DA / DS
Instrument type
Pressure switches
Sensing element
Bourdon tube of brass, 403 SS or 316 SS
Pressure ranges
full vacuum to 8000 psig
Repeatability
±1 % of full operating range; ±1.5 % on DS-7300 models
Deadband
adjustable (DA) or fixed (DS), see model chart
Switch types
SPST mercury, SPDT mercury, SPDT snap switch
Temperature limit
82 °C (180 °F)
Pressure limit
maximum pressure of the operating range
Process connection
1/4″ male NPT (1/2″ male NPT on ranges 15S and 16S); 1/2″ male NPT on explosion-proof units
Conduit connection
1/2″ hole (general purpose), 1/2″ conduit hub (weatherproof), 3/4″ female NPT (explosion-proof)
Electrical connection
screw terminals
Set point adjustment
external thumbscrew
Mounting
vertical
Weight
1.8 kg (general purpose), 2.7 kg (weatherproof), 3.5 kg (explosion-proof)
Approvals
UL, CSA, FM, CE, RoHS
Request a quote
Review enquiry

The DA / DS series are Bourdon tube pressure switches for pressure control in mechanical HVAC systems, pump control, compressors and process equipment. A visible calibrated dial shows the set point, and an on/off indication shows the switch state, so the operating condition can be checked without opening the enclosure. Set points are adjusted externally with a thumbscrew.

Pressure is sensed by a Bourdon tube made of brass, 403 stainless steel or 316 stainless steel, chosen according to the medium and range. As the tube moves with changing pressure, it actuates a mercury switch or a snap-action switch at the set point. On DA models the deadband between switching on and off is adjustable; DS models have a fixed deadband. Values for each range are given in the model charts.

Pressure ranges extend from full vacuum up to 8000 psig. Repeatability is ±1 % of the full operating range, or ±1.5 % on DS-7300 models. The pressure limit equals the maximum pressure of the operating range, and the temperature limit is 82 °C (180 °F). Switch options include SPST mercury, SPDT mercury and SPDT snap-action switches; electrical ratings are listed per model, and wiring is made on screw terminals.

Three enclosure types are offered. The general purpose version has a 1/2″ hole for a conduit hub and weighs 1.8 kg. The weatherproof Series DAW has a 1/2″ conduit hub and weighs 2.7 kg. The explosion-proof Series DAH has a 3/4″ female NPT conduit connection, weighs 3.5 kg and corresponds to NEMA 7 and Class III NEMA 9 and 9A, Division 1. Process connections are 1/4″ male NPT, or 1/2″ male NPT on ranges 15S and 16S and on explosion-proof models. The switches are mounted vertically. They are UL listed, CSA and FM approved (FM approved models are available), and marked CE and RoHS.

Accessories include the 33-25 mounting bracket, remote connections and pigtail siphons; a siphon is required for steam applications at 35 psi or higher. Please state the pressure range, enclosure type, switch type and Bourdon tube material in your enquiry.

Part numbers · 168

DA-7031-153-1, DA-7031-153-2, DA-7031-153-3, DA-7031-153-3A, DA-7031-153-4, DA-7031-153-5, DA-7031-153-6, DA-7031-153-7, DA-7031-153-8, DA-7031-153-9, DA-7021-153-25S, DA-7021-153-26S, DA-7021-153-5S, DA-7021-153-6S, DA-7021-153-8S, DA-7021-153-9S, DA-7021-153-9AS, DA-7021-153-10S, DA-7021-153-11S, DA-7021-153-12S, DA-7021-153-13S, DA-7021-153-15S, DA-7021-153-16S, DA-7041-153-26E, DA-7041-153-23E, DA-7041-153-6E, DA-7041-153-24E, DA-7041-153-9E, DA-7041-153-21E, DA-7041-153-22E, DA-7041-153-11E, DA-7041-153-13E, DA-31-153-2, DA-31-2-2, DA-31-3-2, DA-31-153-3, DA-31-2-3, DA-31-3-3, DA-31-153-27, DA-31-2-27, DA-31-3-27, DA-31-153-1, DA-31-2-1, DA-31-3-1, DA-31-153-3A, DA-31-2-3A, DA-31-3-3A, DA-31-153-4, DA-31-2-4, DA-31-3-4, DA-31-153-5, DA-31-2-5, DA-31-3-5, DA-31-153-6, DA-31-2-6, DA-31-3-6, DA-31-153-7, DA-31-2-7, DA-31-3-7, DA-31-153-8, DA-31-2-8, DA-31-3-8, DA-31-153-9, DA-31-2-9, DA-31-3-9, DA-21-153-25S, DA-21-2-25S, DA-21-3-25S, DA-21-153-26S, DA-21-2-26S, DA-21-3-26S, DA-21-153-5S, DA-21-2-5S, DA-21-3-5S, DA-21-153-6S, DA-21-2-6S, DA-21-3-6S, DA-21-153-8S, DA-21-2-8S, DA-21-3-8S, DA-21-153-9S, DA-21-2-9S, DA-21-3-9S, DA-21-153-9AS, DA-21-2-9AS, DA-21-3-9AS, DA-21-153-10S, DA-21-2-10S, DA-21-3-10S, DA-21-153-11S, DA-21-2-11S, DA-21-3-11S, DA-21-153-12S, DA-21-2-12S, DA-21-3-12S, DA-21-153-13S, DA-21-2-13S, DA-21-3-13S, DA-21-153-15S, DA-21-2-15S, DA-21-3-15S, DA-21-153-16S, DA-21-2-16S, DA-21-3-16S, DA-41-153-26E, DA-41-2-26E, DA-41-3-26E, DA-41-153-23E, DA-41-2-23E, DA-41-3-23E, DA-41-153-6E, DA-41-2-6E, DA-41-3-6E, DA-41-153-24E, DA-41-2-24E, DA-41-3-24E, DA-41-153-9E, DA-41-2-9E, DA-41-3-9E, DA-41-153-21E, DA-41-2-21E, DA-41-3-21E, DA-41-153-22E, DA-41-2-22E, DA-41-3-22E, DA-41-153-11E, DA-41-2-11E, DA-41-3-11E, DA-41-153-13E, DA-41-2-13E, DA-41-3-13E, DS-7231-153-2, DS-7231-153-3, DS-7231-153-27, DS-7231-153-1, DS-7231-153-3A, DS-7231-153-4, DS-7231-153-5, DS-7231-153-6, DS-7231-153-7, DS-7231-153-8, DS-7231-153-9, DS-7221-153-25S, DS-7221-153-26S, DS-7221-153-5S, DS-7221-153-6S, DS-7221-153-8S, DS-7221-153-9S, DS-7221-153-9AS, DS-7221-153-10S, DS-7221-153-11S, DS-7221-153-12S, DS-7221-153-13S, DS-7221-153-15S, DS-7221-153-16S, DS-7241-153-26E, DS-7241-153-23E, DS-7241-153-6E, DS-7241-153-24E, DS-7241-153-9E, DS-7241-153-21E, DS-7241-153-22E, DS-7241-153-11E, DS-7241-153-13E, DAW-33-153-7, DAH-31-153-7, DAF-31-153-7, DAHF-31-153-7

Industry applications

Selection notes

Specify whether the reference is gauge, absolute or differential pressure. Include the normal span and the largest pressure the instrument may see.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments