DwyerOmega FST1000
DwyerOmega

FST1000 air flow switch with high and low alarm relays

Flow switches & indicators

Manufacturer
DwyerOmega
Model
FST1000
Instrument type
Flow switches & indicators
Sensing principle
hot-wire air velocity sensor with RTD elements, bi-directional
Air velocity range
0–5000 FPM (0–25.4 m/s) or 0–10,000 FPM (0–50.8 m/s)
Accuracy
2 % of full scale
Response time
250 ms
Alarm outputs
2 SPST NO relays, adjustable high and low set points
Alarm deadband
5 % of full scale
Contact rating
10 A at 24 V DC; 10 A at 250 V AC
Power supply
15 to 24 V DC, 200 mA
Ambient temperature
0 to 50 °C
Probe temperature
−40 to 93 °C
Probe material
304 stainless steel
Connections
compression fitting; screw terminals
Dimensions
89 × 51 × 31.8 mm
Weight
160 g
Request a quote
Review enquiry

The FST1000 series is an economical air flow switch that measures air velocity and provides two relay contact closures for high and low alarm set points. It is designed for use with clean air or nitrogen only and is applied wherever an air flow must be verified and an alarm raised if it becomes too high or too low.

The sensor uses a hot-wire design based on RTD elements. Air velocity is determined from the heat loss of the heated RTD sensor as it is cooled by the passing air: the higher the velocity, the greater the cooling. The device is bi-directional and gives the same readings for forward or reverse flow.

Two velocity ranges are available. FST1001 models cover 0 to 5000 FPM (0 to 25.4 m/s) and FST1002 models cover 0 to 10,000 FPM (0 to 50.8 m/s). Accuracy is 2 % of full scale, and the response time is 250 ms, so changes in air flow are detected quickly.

The outputs are two SPST normally open relay contacts with adjustable high and low alarm set points and an alarm deadband of 5 % of full scale. Each contact is rated 10 A at 24 V DC or 10 A at 250 V AC. A green LED indicates power and red LEDs indicate alarm states. The switch requires 15 to 24 V DC at 200 mA; a matching 24 V DC power supply is offered, for example PSR-24S or PSR-24L.

The probe is made of 304 stainless steel and is installed with a compression fitting; electrical connections are made on screw terminals. The electronics operate at ambient temperatures from 0 to 50 °C, while the sensor probe tolerates −40 to 93 °C. The housing measures 89 × 51 × 31.8 mm and weighs 160 g.

Versions are available with a fixed probe (suffix -A) or a remote probe with a 12-inch long probe (suffix -R); a short probe of 95 mm is designated with the suffix -S. Typical applications are HVAC monitoring, exhaust and ventilation hoods and manufacturing processes that require airflow verification. Please state the required velocity range, the probe version and the supply voltage available when you send an enquiry.

Part numbers · 9

FST1001A, FST1001R, FST1002A, FST1002R, TX8-100, PSR-24S, PSR-24L, SSLK-14-14, TFER-1/4

Industry applications

Selection notes

State the minimum, normal and peak flow with units. Pipe bore, fluid properties and the available straight run affect the choice of measuring principle.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment

DEVICEEU