DwyerOmega GSTC
DwyerOmega

GSTC carbon monoxide and nitrogen dioxide gas transmitter

Gas detectors & alarms

Manufacturer
DwyerOmega
Model
GSTC
Instrument type
Gas detectors & alarms
Measured gas
carbon monoxide (GSTC-C) or nitrogen dioxide (GSTC-N)
Sensor
field-replaceable electrochemical
Sensor life
2 years
Drift
< 5 % per year in air
Coverage area
5000 to 7500 sq ft
Communication
RS-485, BACnet MS/TP, Modbus RTU, Modbus ASCII (field-selectable)
Supply voltage
11 to 36 V DC or 21.6 to 33 V AC (isolated), 5.7 mA at 24 V DC
Display
optional integral LCD; remote LCD A-449
Operating temperature
−4 to 122 °F
Humidity
15–90 % RH constant; 0–99 % RH intermittent
Housing
UV-resistant glass-filled polycarbonate, IP64
Mounting
wall or duct
Electrical connection
conduit knockouts with terminal block
Weight
1 lb
Approvals
CE, RoHS
Request a quote
Review enquiry

The GSTC series is a gas transmitter for monitoring carbon monoxide (CO) or nitrogen dioxide (NO2) concentrations in mechanical rooms, underground parking garages and loading docks. CO models detect exhaust from gasoline engines, and NO2 models detect exhaust from diesel engines.

The transmitter uses a field-replaceable electrochemical sensor. The sensor life is two years and drift is less than 5 % per year in air. When the sensor reaches the end of its life, it is replaced with an A-505 CO sensor or an A-506 NO2 sensor. One transmitter covers an area of 5000 to 7500 sq ft.

Communication is over RS-485, with field-selectable BACnet MS/TP, Modbus RTU or Modbus ASCII protocols, according to TIA-EIA-485-A and ANSI/ASHRAE Standard 135-2010. Power is supplied with 11 to 36 V DC or 21.6 to 33 V AC, isolated, with a current of 5.7 mA at 24 V DC.

Calibration can be carried out on site, using the onboard push-buttons or the optional A-449 remote LCD display. An integral LCD display is available as an option.

The housing is made of UV-resistant glass-filled polycarbonate and rated IP64. The transmitter operates from −4 to 122 °F at 15 to 90 % RH constant, or 0 to 99 % RH intermittent, and weighs 1 lb. Electrical connection is made on a terminal block accessed through conduit knockouts. It can be wall-mounted or duct-mounted. CE and RoHS conformity is stated.

Models are GSTC-C for carbon monoxide and GSTC-N for nitrogen dioxide, each available without display, with the -D option or with an integral LCD (-LCD), for example GSTC-C-LCD or GSTC-N-D.

Applications named for the transmitter are garage ventilation, loading dock monitoring and mechanical room monitoring. When you send an enquiry, please state the gas to be monitored, the area to be covered, the mounting type, the communication protocol and whether a display is required.

Part numbers · 6

GSTC-C, GSTC-C-D, GSTC-C-LCD, GSTC-N, GSTC-N-D, GSTC-N-LCD

Industry applications

Selection notes

Identify the target gas, background gas and concentration units. State whether the sampling system is already installed or belongs in the enquiry.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.