Type 8189
Level

Float & magnetic level indicators
The Model J52 is a refrigerant liquid level switch with a float-actuated external cage mechanism. It provides level alarm and pump control on liquid accumulators and receivers and is designed for liquids with a specific gravity of 0.60 and above, including ammonia, Freon, methyl chloride and sulphur dioxide.
The switch works magnetically. A float in the chamber is connected to an attraction sleeve. As the liquid level rises, the float raises the sleeve into the field of a permanent magnet attached to a pivoted switch actuator; the magnet snaps against the non-magnetic enclosing tube and actuates the switch. When the level falls, the sleeve moves out of the field and a return spring deactivates the switch. The switching output is SPDT.
The switch is rated for operating temperatures from −50 to +100 °F (−45 to +40 °C) and a maximum working pressure of 400 psig (28 bar). The float chamber is a welded assembly, and connections are 3/4 in NPT or 3/4 in socket weld. The housing is completely sealed against moisture, with a conduit seal and 24 in (610 mm) lead wires.
Housing options are NEMA 4X steel, NEMA 4X/7/9 explosion-proof and NEMA 4 transparent versions. An optional cryogenic insulation is available. The switch must be mounted within 3° of vertical. For low-temperature liquids, the chamber and piping should be insulated to prevent boiling in the float chamber.
Approvals listed include FM, CSA, EAC and SIL, and production is to ISO 9001. Articles include J52-4101-002, J52-4102-002, J52-4107-004, J52-4111-002 and J52-4112-002.
Applications named are ammonia storage, catalysis vessels, chemical reactors, deionisation tanks, heat recovery steam generators in power utilities and petroleum refining. Please state the liquid, the operating pressure and temperature, the connection type and the housing version in your enquiry.
J52-4101-002, J52-4107-004, J52-4102-002, J52-4112-002, J52-4111-002
Identify the vessel height, nozzle position and surface conditions. A point alarm and a continuous level reading require different outputs.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.