LUMEL ND31PLUS
LUMEL

ND31PLUS power network meter with dual Ethernet

Power quality analysers

Manufacturer
LUMEL
Model
ND31PLUS
Instrument type
Power quality analysers
Measured parameters
54, including current and voltage harmonics up to 63rd
Network configuration
1-phase 2-wire; 3-phase 3- or 4-wire, balanced and unbalanced
Accuracy class
0.2S for active energy
Ethernet
2 × RJ45, 10/100 Mbit/s, daisy chain
Protocols
MQTT, BACnet/IP, Modbus TCP/IP
Serial interface
RS-485, Modbus
Analogue output
0/4–20 mA
Alarm outputs
2, configurable
Temperature inputs
2 × Pt100
Display
3.5-inch TFT colour LCD, 640 × 480 pixels
Memory
8 GB, archiving of 32 parameters
Functions
time of use (ToU)
Dimensions
96 × 96 × 77 mm
Approvals
CE
Request a quote
Review enquiry

The ND31PLUS is an enhanced power network meter for modern industrial installations. Its main feature is a pair of Ethernet ports with daisy-chain topology: several meters can be connected in a serial chain without external switches, which saves space and cabling cost in the switchboard.

The meter measures 54 power network parameters, including current and voltage harmonics up to the 63rd order. It can be configured for 1-phase 2-wire networks or for 3-phase 3-wire or 4-wire networks, balanced or unbalanced. Active energy is measured in accuracy class 0.2S, and a time of use (ToU) function supports energy monitoring.

Communication is provided through two RJ45 Ethernet ports at 10/100 Mbit/s (10Base-T/100Base-TX). The protocols MQTT, BACnet/IP and Modbus TCP/IP are programmable. In addition, an RS-485 interface with Modbus protocol is available.

Further I/O includes an analogue output of 0/4–20 mA, two configurable alarm outputs and two Pt100 inputs for temperature measurement. Readings are shown on a 3.5-inch TFT graphical colour display with a resolution of 640 × 480 pixels. The 8 GB internal memory is used for archiving 32 parameters.

The meter is housed in a 96 × 96 mm panel case with an overall depth of 77 mm and is CE-marked. Parameters are programmed with free configuration software.

Versions are selected according to the network type: 1-phase 2-wire, 3-phase 3-wire or 3-phase 4-wire configuration. In a daisy chain, the two RJ45 ports of each meter link it to the previous and the next device, so no external Ethernet switch is needed between the meters.

Applications named for the ND31PLUS are large switchboards, production lines, energy installations and applications where space and time are critical. When you send an enquiry, please specify the network configuration, the rated voltages and currents, the communication protocol you will use and the required number of meters.

Part numbers · 1

ND31PLUS

Industry applications

Selection notes

Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment

DEVICEEU