Type 8189
Level

Conductive & optical level switches
The Opto-Pak controller is a relay module that expands the power and switching capabilities of 12 V DC electro-optic level switches. It allows such switches to be operated from line voltage and to switch moderate electrical loads directly, without a separate power supply and interposing relay.
The module converts the standard 115 V AC line supply into the 12 V DC needed by compatible switches and evaluates the switch signal. When the level switch changes state, the module operates its SPDT relay, whose contacts can then switch the connected load. Built-in LEDs show the presence of power and the status of the relay.
The input voltage is 115 V AC ±10 %, 50/60 Hz, and the maximum current draw is 70 mA at 120 V AC. The SPDT relay output is rated 5 A at 115 V AC and 5 A at 30 V DC. The module operates over a wide temperature range from −25 to +70 °C (−13 to +158 °F).
Compatible switches are the ELS-1100, ELS-1150, ELS-1200 and ELS-300 series of electro-optic level switches.
Two versions are available. Part number 149536 is supplied as an open circuit board for mounting inside an existing enclosure or panel. Part number 149535 is supplied in a NEMA 4X junction box enclosure measuring 125.4 × 75.4 × 96.8 mm (4-15/16 × 2-31/32 × 3-13/32 in), for installation where the module needs its own protective housing.
Electrical connections are made with 1/4 in male spade terminals, which allows straightforward wiring; ten female spade connectors are shipped loose with the module.
The intended use is control of moderate electrical loads in level switching systems based on electro-optic switches through the relay contacts within their rating.
Please state the version required (open board or NEMA 4X enclosure), the switch model it will be used with and the quantity.
149536, 149535
Identify the vessel height, nozzle position and surface conditions. A point alarm and a continuous level reading require different outputs.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.