Gems Sensors & Controls PS11
Gems Sensors & Controls

PS11 low-pressure diaphragm switch with snap-action microswitch

Pressure switches

Manufacturer
Gems Sensors & Controls
Model
PS11
Instrument type
Pressure switches
Pressure range
0.75–4 psi (51–276 mbar) per data; series 0.75 to 15 psi (0.051 to 1 bar)
Set point
Adjustable or factory set
Switch
SPST N.O., SPST N.C. or SPDT; 5 A at 24 VDC and 250 VAC
Contacts option
Gold contacts (option G)
Cycle life
1,000,000 cycles typical
Proof pressure
0 psia to 150 psi (−1 to 10.3 bar)
Burst pressure
300 psi (20.7 bar)
Housing / fitting
Brass
Diaphragm
Nitrile; optional Viton, EPDM or Kapton
O-ring
Nitrile; optional Viton or EPDM
Pressure fittings
1/8" NPTM, 1/4" NPTM, 1/4" BSPM, 7/16"-20 SAE male
Terminations
DIN 43650A, flying leads, 1/2" NPT conduit, Weather Pack, Deutsch
Operating temperature
−40 to 250 °F (−40 to 121 °C), by diaphragm
Weight
Approx. 0.31 lb (0.14 kg)
Approvals
CE; UL approved units available
Request a quote
Review enquiry

The PS11 series is a low-pressure switch for general-purpose applications in which small pressures must be detected reliably. It was formerly known as PDPA/PDPF. The switches have a typical life expectancy of one million cycles.

System pressure acts on a diaphragm, which operates a snap-action microswitch when the set point is reached; the microswitch resets automatically when the pressure falls back. The set point can be adjustable or set at the factory. The brass housing provides chemical resistance, while the diaphragm material determines the permissible operating temperature range.

The pressure range listed for the configured variants is 0.75 to 4 psi (51 to 276 mbar); the series as a whole covers set points from 0.75 to 15 psi (0.051 to 1 bar). Proof pressure is from 0 psia (vacuum) up to 150 psi (−1 to 10.3 bar), and burst pressure is 300 psi (20.7 bar).

The microswitch is available as SPST normally open, SPST normally closed or SPDT and is rated 5 A at 24 VDC and 250 VAC; gold contacts are available as option G. Electrical terminations include a DIN 43650A connector (with 9 mm cable clamp, with 1/2" female NPT conduit or as male half only), flying leads, a 1/2" male NPT conduit with flying leads, and Weather Pack or Deutsch connectors. The ingress protection of the open terminations is IP00.

Wetted parts are a brass fitting, a nitrile diaphragm (Viton, EPDM or Kapton optional) and a nitrile O-ring (Viton or EPDM optional). The recommended temperature limits are 15 to 250 °F for nitrile, 0 to 250 °F for Viton, −20 to 250 °F for EPDM and −40 to 250 °F for Kapton, giving an overall range of −40 °F to 250 °F (−40 °C to 121 °C). Pressure fittings are 1/8" NPTM, 1/4" NPTM, 1/4" BSPM and 7/16"-20 SAE male, all in brass. The switch has a diameter of 1.77" (45 mm) and weighs about 0.31 lb (0.14 kg). CE marking applies and UL approved units are available. More than 140 configured variants are listed, with a configuration code such as PS11-10-4MNB-C-HC-XX-XXXX.

When enquiring, please state the set point and switching direction, circuit, diaphragm material, fitting, termination and quantity, or the full configuration code.

Part numbers · 26

141 configured variants, 221025, 210887, 623358, 623405, 262950, W1105845, 623406, 623349, 256553, 623365, 208745, 623362, 623352, 212388, 623394, 623333, 209737, 623324, 623395, 215898, 623357, 213716, 210658, 221193, 623378

Industry applications

Selection notes

Specify whether the reference is gauge, absolute or differential pressure. Include the normal span and the largest pressure the instrument may see.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment

DEVICEEU