EDT 101
Temperature

Thermostats & temperature switches
The RH51 and RH52 are limit value switches for temperature that work with NTC thermistor sensors. They monitor the sensor signal and switch a volt-free relay contact when an adjustable temperature limit is reached. The compact, robust devices are designed for harsh environments and for marine applications, where they carry DNV, LR and BV approvals.
An NTC thermistor changes its resistance strongly with temperature, its resistance falling as the temperature rises. The switch continuously evaluates this resistance; when the temperature passes the limit set on the drum scale, the internal relay operates. Besides the limit value, the device also monitors the sensor circuit for short circuit and wire break, and an integrated LED indicates operating status and faults.
Two setting ranges are available: 40 to 120 °C for the RH51 and 5 to 70 °C for the RH52. The output is a volt-free changeover contact with normally closed function; the RH51-A and RH52-A versions have the contact as changeover in normally open function. Switching capacity is 30 W in DC circuits (1 A at 30 V DC or 0.5 A at 60 V DC) and 40 W in AC circuits (0.2 A at 220 V AC).
The devices are supplied with 18 to 32 V DC. Electrical connection uses gold-plated tab connectors A6.3 × 0.8 to DIN 46244. The housing is made of green thermoplastic polyester with fire protection class V0, and the switch snaps onto a TS32 G-rail or a TS35 top-hat rail. It weighs 55 g, operates at ambient temperatures from −20 °C to +70 °C and withstands humidity of up to 96 %.
The design is tested to a long list of standards, including the IEC 60068 series for vibration, shock and damp heat, IEC 61000-4-2 to -4-6 for EMC immunity, CISPR 16 for emission, IEC 60553, DIN EN 60529, DIN EN 61000-6-2 and -6-4 and the railway standards DIN EN 50155 and DIN EN 50035. The device carries the CE mark.
Listed fields of use are temperature monitoring in marine applications and harsh environments.
Please state the required setting range, the contact function (normally closed or normally open) and the NTC sensor type to be connected when requesting a quotation.
RH51, RH52, RH51-A, RH52-A
Match the sensing element, insertion length and wiring to the existing input. Separate the process temperature from the ambient temperature at the connection head.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.