SENECA S504C-6
SENECA

S504C-6 three-phase MID energy meter for CT connection with communication

Energy meters

Manufacturer
SENECA
Model
S504C-6
Instrument type
Energy meters
Voltage
3 × 230/400 V … 3 × 240/415 V, 50/60 Hz
Wiring
3-phase, 3 or 4 wires, 2 or 3 CTs
Current
1 or 5 A CT secondary; Imax 6 A, In 1 A, Ist 1 mA
CT ratio
1 to 10000
Active energy accuracy
class 1 (IEC/EN 62053-21); class B MID (EN 50470-3); class C for S504C6-ETH-MID-N
Reactive energy accuracy
class 2 (IEC/EN 62053-23)
Communication
RS485 Modbus, M-Bus or 10/100Base-T Ethernet (Modbus TCP, HTTP, NTP, DHCP), by version
S0 output
passive, optically isolated, 50 ±2 ms ON
Meter constant
10000 imp/kWh
Consumption
max. 3.5 VA – 1 W per phase; current circuit 0.04 VA
Insulation
4 kV; impulse voltage 6 kV; protective class II
Protection
IP51 in cabinet
Operating temperature
−25 to +55 °C
Weight
0.4 kg (gross)
Request a quote
Review enquiry

The S504C-6 is a compact three-phase energy meter in a 4-DIN-module housing, designed for industrial and residential installations where energy has to be measured through current transformers and read remotely. It is available in MID certified versions with an integrated RS485 Modbus, M-Bus or Ethernet port, so the measured data can be transmitted to a remote station.

The meter measures voltage, current, power factor and active, reactive and apparent energy, and shows totalisers and instantaneous power values on its LCD screen. A partial counter can be reset, and tariff management is supported. The device is self-powered from the measuring circuit, so no separate auxiliary supply is needed. Currents are taken from current transformers with a 1 A or 5 A secondary; the CT ratio can be set from 1 to 10000.

The meter is connected to three-phase networks of 3 × 230/400 V to 3 × 240/415 V at 50/60 Hz, in three-wire or four-wire configuration with two or three CTs. The reference current is 1 A and the maximum current 6 A, with a starting current of 1 mA, a minimum current of 10 mA and a transitional current of 50 mA. Active energy is measured to class 1 according to IEC/EN 62053-21 and class B according to EN 50470-3 (MID); the S504C6-ETH-MID-N version is class C. Reactive energy is measured to class 2 according to IEC/EN 62053-23. Consumption is at most 3.5 VA or 1 W per phase and the current circuit burden 0.04 VA.

The passive, optically isolated S0 output delivers pulses of 50 ±2 ms with a minimum OFF time of 30 ms, at a constant of 10000 pulses per kWh. Ethernet versions communicate at 10/100 Mbps and support Modbus TCP, HTTP with a web server, NTP and DHCP; the default IP address is 192.168.1.249.

The housing material meets UL 94 class V0; the meter has protective class II, pollution degree 2, a rated impulse voltage of 6 kV and an insulation voltage of 4 kV. IP51 protection is achieved when it is installed in a cabinet rated IP51 or higher. Measuring terminals take 1.5 to 6 mm², S0 terminals 0.14 to 1.5 mm². The operating temperature is −25 to +55 °C at up to 80 % humidity without condensation and up to 2000 m altitude. The meter carries CE marking and MID approval and complies with EN IEC 62052-11, IEC 62052-31, EN 50470-3, EN 62059-32-1, DIN 43880 and CISPR 32 class A.

Ordering versions are S504C-6-MOD-MID with Modbus, S504C-6-MBU-MID with M-Bus, and S504C-6-ETH-MID and S504C6-ETH-MID-N with Ethernet. Typical uses are energy measurement and consumption monitoring in industrial plants and residential buildings and tariff management. Please state the network type, CT ratio and required communication port in your enquiry.

Part numbers · 4

S504C-6-MBU-MID, S504C-6-MOD-MID, S504C6-ETH-MID-N, S504C-6-ETH-MID

Industry applications

Selection notes

Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.