Gems Sensors & Controls STB 55
Gems Sensors & Controls

STB 55 safety temperature limiter, SIL 2 and DIN EN 14597

Thermostats & temperature switches

Manufacturer
Gems Sensors & Controls
Model
STB 55
Instrument type
Thermostats & temperature switches
Certification
DIN EN 14597; SIL 2 (EN 61508)
Inputs
Pt100; thermocouple J, K, N, S
Relays
safety relay; separate pre-alarm relay (1 or 2 alarm relays)
Analogue output
optional 0/4…20 mA or 0/2…10 V DC
Accuracy
< 0.5 %, ±2 digits
Reaction time
≤ 0.5 s
Display
graphic LCD, plain-text fault messages
Functions
password protection, external reset input
Power supply
230 V AC, 115 V AC, 24 V AC ±10 %; 24 V DC ±15 %
Power consumption
< 4 VA
Operating temperature
−10 to 55 °C
Relative humidity
< 95 %
Protection
IP20
Mounting
DIN EN 60715 TS35 rail
Weight
approx. 450 g
Request a quote
Review enquiry

STB 55 is a safety temperature limiter for the protection of industrial thermal systems. It monitors the temperature of a process and switches off the equipment when unsafe conditions occur. The device is certified to DIN EN 14597 for temperature limiters and to SIL 2 according to EN 61508, for use in safety-related temperature monitoring.

Temperature is measured with a Pt100 sensor or with a type J, K, N or S thermocouple. When the permissible limit is reached, or when a fault such as a sensor failure occurs, the STB 55 switches off the equipment without delay through its safety relay; the reaction time is 0.5 s or less. At the same time the alarm relays are activated and the fault is shown as a plain-text message on the graphic LCD. A separate pre-alarm relay can warn before the safety limit is reached. An external reset input is provided.

Measuring accuracy is better than 0.5 %, ±2 digits. Depending on the version, the device has one or two alarm relays in addition to the safety function, and an optional analogue output of 0/4…20 mA or 0/2…10 V DC transmits the measured value to a controller or recorder. Settings are protected by a password to prevent unauthorised changes.

Supply versions are available for 230 V AC, 115 V AC and 24 V AC (±10 %, 50–60 Hz) and for 24 V DC (±15 %); power consumption is below 4 VA. The device operates from −10 to 55 °C and can be stored from −30 to 60 °C at relative humidity below 95 %. The housing has IP20 protection according to DIN EN 60529 and is mounted on a DIN EN 60715 TS35 rail; it weighs approximately 450 g. EMC conformity follows EN 61326-1 and EN 61326-2-2, and the device carries CE marking.

Listed versions include STB55-5000-000, STB55-1050-000, STB55-5250-000 and STB55-5050-000, which differ in input type, number of relays, analogue output and supply voltage.

Listed applications are industrial thermal systems and exhaust gas temperature monitoring. Please state the sensor type, supply voltage, number of alarm relays and whether an analogue output is required in your enquiry.

Part numbers · 4

STB55-5000-000, STB55-1050-000, STB55-5250-000, STB55-5050-000

Industry applications

Selection notes

Match the sensing element, insertion length and wiring to the existing input. Separate the process temperature from the ambient temperature at the connection head.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment

DEVICEEU