Gems Sensors & Controls TB 40-1
Gems Sensors & Controls

TB 40-1 safety temperature limiter for heating and refrigeration

Thermostats & temperature switches

Manufacturer
Gems Sensors & Controls
Model
TB 40-1
Instrument type
Thermostats & temperature switches
Function
safety temperature limiter for heating and cooling
Inputs
thermocouples, RTDs, current, voltage
Resolution
> 14 bit
Scanning cycle
100 ms
Supply voltage
90–260 V AC, 48–62 Hz; 20.4–26.4 V AC; 18–31 V DC
Power consumption
approx. 7 VA
Output contacts
max. 500 VA, 250 V AC, 2 A
Electrical life
800,000 duty cycles (output 1); 600,000 (output 2)
Input impedance
≥ 1 MΩ
Front protection
IP65, NEMA 4X; housing IP20, terminals IP00
Mounting
panel, two fixing clamps; plug-in modules
Standards
EN 14597, EN 61010-1, EN 61326-1, DIN 4751, DIN 4752, DIN 4754, DIN 4755
Approvals
CE, cULus
Request a quote
Review enquiry

The TB 40-1 is a safety temperature limiter for heating and cooling applications. Its job is to protect heat-generating systems from unsafe temperatures: if the adjusted limit is reached, or if a sensor break or short circuit is detected, it interrupts power immediately via potential-free contacts. The limiter is certified to EN 14597 for use in hazardous applications.

The instrument has a universal input that accepts thermocouples, RTDs, current and voltage signals. The input is converted with a resolution of more than 14 bits, the scanning cycle is 100 ms and the input impedance is at least 1 MΩ. Once the limiter has tripped, it stays off until it is reset; the limit settings and the reset function are password-protected, so the safety setting cannot be changed by unauthorised persons.

The output relays are rated up to 500 VA, 250 V AC and 2 A. The electrical life is 800,000 duty cycles for the first output and 600,000 duty cycles for the second. Minimum switching values are 6 V / 1 mA DC for output 1 and 5 V / 10 mA AC/DC for output 2. Power supply versions are available for 90–260 V AC at 48–62 Hz, 20.4–26.4 V AC and 18–31 V DC; consumption is approximately 7 VA.

A front interface allows connection to a PC through an adapter, and configuration software is available in Mini, Basic and Expert versions. The front panel is protected to IP65 and NEMA 4X, the housing to IP20 and the terminals to IP00. The unit is panel-mounted with two fixing clamps, and its plug-in module design allows modules to be replaced quickly without tools. A standard rail adapter is also offered.

The limiter complies with EN 14597, EN 61010-1, EN 61326-1 and DIN 4751, 4752, 4754 and 4755 and is marked CE and cULus. Several ordering codes cover the different configurations, for example TB401110000EU00 and TB401000000EU00.

Typical applications are heat-generating plants, hot-water plants, thermal transfer plants and oil-heated plants. Please send the sensor type, the supply voltage and the required ordering code or configuration with your enquiry.

Part numbers · 8

TB401110000EU00, TB401000000EU00, TB4010000000D00, TB401010000E000, TB401100000EU00, TB4011000090U00, TB401000000E000, TB401020000ED00

Industry applications

Selection notes

Match the sensing element, insertion length and wiring to the existing input. Separate the process temperature from the ambient temperature at the connection head.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.

Related instruments

Find equipment

DEVICEEU