EDT 101
Temperature

Temperature transmitters
This series of single-point temperature transmitters combines a stainless steel bullet probe on a plenum-rated cable with a transmitter in a separate enclosure. It measures air temperature in roof top units and air handlers, in discharge, supply, return and mixed air ducts, and is also used for remote temperature sensing.
The sensing element is a platinum RTD to DIN EN 60751 (IEC 751), mounted in a 304 stainless steel bullet probe of 0.25 in diameter with an insertion length of 1 in and a neoprene fitting. The RTD itself operates from −40 to 200 °C, while the transmitter process range is −40 to 150 °C. The measuring span is specified with the order, for example −30 to 130 or 40 to 90.
Accuracy is ±0.2 % for spans below 260 °C and ±0.5 % for spans above 500 °F (260 °C). All transmitters include zero and span adjustments for field calibration, and NIST-certified calibration options are available.
The standard output is a two-wire, loop-powered 4–20 mA current signal. As an option, a three-wire voltage output of 1–5 V DC or 2–10 V DC can be selected. The supply voltage is 8.5 to 32 V DC, with a minimum supply current of 25 mA. Wiring is made on screw terminals. The transmitter operates at 0 to 95 % RH non-condensing and may be stored from −40 to 80 °C.
Several sensor series are available: TT100, TT1K, TTM100 and TTM1K. The transmitter enclosure can be galvanised steel, plastic, aluminium or NEMA 4X; depending on the version, ratings range from NEMA 1 and IP10 to NEMA 3R and NEMA 4X. The plenum-rated lead wire is offered in lengths of 6, 10 and 20 ft. Mounting hardware such as the A/MOUNTING CLIP-1/4″ and A/MOUNTING U-CLIP-1/4″ is available as an accessory. The products comply with RoHS2 and WEEE.
When ordering, please specify the sensor series, the required temperature span, the output signal, the enclosure type and the cable length.
A/TT100-BP-1-GD-10'CL2P, A/TT100-BP-1-PB-10CL2P, A/TT100-BP-2-GD-20'CL2P, A/TT100-BP-4-4X-6'CL2P, A/TT100-BP-4-GD-20'CL2P, A/TT100-BP-4-PB-20'CL2P, A/TT1K-BP-1-GD-10'CL2P, A/TT1K-BP-2-4X-20'CL2P, A/TT1K-BP-2-GD-6'CL2P, A/TT1K-BP-4-4X-10'CL2P, A/TT1K-BP-4-4X-20'CL2P, A/TT1K-BP-4-GD-10'CL2P, A/TT1K-BP-4-GD-20'CL2P, A/TT1K-BP-4-PB-10'CL2P, A/TT1K-BP-4-PB-6'P, A/TTM100-BP-1-GD-10'CL2P, A/TTM100-BP-1-PB-20'CL2P, A/TTM100-BP-4-GD-10'CL2P, A/TTM1K-BP-4-4X-10'CL2P, A/TTM1K-BP-4-4X-20'CL2P, A/TTM1K-BP-4-4X-6'CL2P, A/TTM1K-BP-4-GD-20'CL2P, A/TTM1K-BP-4-PB-10'CL2P, 143351, 143352
Match the sensing element, insertion length and wiring to the existing input. Separate the process temperature from the ambient temperature at the connection head.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.