DTL C
Electrical test & measurement

Insulation & earth testers
The 1577 is a portable, battery-powered true-RMS insulation multimeter with a 6000-count display. It combines an insulation tester and a digital multimeter in one handheld instrument and is designed for troubleshooting and testing motors, generators, cables and switchgear, as well as fixed installations at the distribution level, the primary supply level and variable frequency motor drives.
For insulation testing, the meter applies a selected test voltage of 500 V or 1000 V to the circuit and measures the resulting insulation resistance from 0.1 MΩ to 600 MΩ. Accuracy at 500 V and 1000 V is ±(2.0 % + 5), and the minimum test current is 1 mA at 1 kΩ/V. Live circuit detection prevents an insulation test if a voltage above 30 V is present, and capacitive voltage is discharged automatically after the test. PI and DAR testing capability is listed for the series. With fresh alkaline batteries at room temperature the meter performs at least 1000 insulation tests of 1000 V into 1 MΩ with 5 s on and 25 s off.
As a multimeter, it measures true-RMS AC and DC voltage up to 1000 V, AC and DC current up to 400 mA with 0.01 mA resolution, and resistance up to 50 MΩ with 0.1 Ω resolution. A low-pass filter allows voltage measurements on variable frequency drives.
The instrument is rated CAT IV 600 V and CAT III 1000 V to IEC 61010-2-033, pollution degree 2, and the mA input is fused with 0.44 A, 1000 V, 10 kA. It complies with IEC 61326-1 and -2-2 for EMC and carries CSA and TÜV marks. Power comes from four AA batteries. It operates from −20 to +55 °C up to 2000 m, is stored from −40 to +60 °C, and is protected to IP40. With holster it measures 203 × 100 × 50 mm and weighs 624 g.
Accessories include a remote probe, test leads, alligator clips and a hard case. The related 1587 and 1587 FC models extend the insulation range to 0.01 MΩ to 2 GΩ with test voltages of 50, 100, 250, 500 and 1000 V.
Please state the model and required accessories when enquiring.
1577
Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.