AHD 514 OP / AHD 514 OP B
Industrial automation & edge AI

Programmable logic controllers
The AMC 300 is an advanced programmable automation controller (PAC) designed for resilient operation in marine and offshore environments and in power generation. It is a Linux-based PLC platform with a modular architecture: the controller is assembled in racks with power supply and I/O modules and can be extended with further racks. A design lifetime of ten years is stated.
The controller uses EtherCAT as its native communication protocol for distributed I/O, and it is programmed with CODESYS V3.5 according to IEC 61131-3. Further protocols listed are CANopen, CAN, Modbus TCP, PROFINET and OPC UA, and the Ethernet interface supports TCP/IP with SSH and SCP; RS-422 is also available. For reliable operation the controller has a fail-safe start-up with dual operating system images, secure boot and signed software updates.
A notable feature for power applications is direct measurement of a 690 V AC three-phase grid; the voltage measuring range is 2 to 897 V AC. This allows the controller to be used for genset and engine control, grid connection with or without synchronisation, and power and energy management.
Two rack sizes are available. The R4.1 has four slots and measures 146.1 × 199.9 × 157.5 mm, weighing 1457 g with minimum hardware; the R7.1 has seven slots, measures 230.1 × 199.9 × 157.5 mm and weighs 2283 g. The controller is mounted on DIN rail or base-mounted with four M6 bolts with self-locking washers, and is supplied pre-assembled in racks.
The hardware is designed for harsh conditions: cold start-up and operation from −40 °C to 70 °C, storage from −40 °C to 85 °C, 55 °C at 97 % RH condensing, altitude below 4000 m, vibration of 2.1 g (3.2–50 Hz) and 1.0 g (13.2–100 Hz), shock of 50 g for 11 ms and bump of 25 g for 6 ms. It complies with IEC 60945 and IACS UR E10 for marine use and with UL508, UL6200, CSA C22.2 No. 14-13 and No. 142, EN 61010-1, IEC/EN 60255-27 and the EN 61000-6-2/-6-3 EMC standards, and carries CE, UL and CSA marks.
Listed applications include marine and offshore power management, hybrid and microgrid systems, diesel electric propulsion, wind turbine retrofit, steam turbine speed governing, fuel cells, solar and storage, and data centres and hospitals; installation on ship bridges and in switchboards of ferries, offshore vessels, fishing vessels, yachts and offshore platforms is listed.
Please send the planned application, the required I/O modules and rack size, and the communication interfaces with your enquiry.
4921240613G
List the field signals, controller family and runtime environment. For edge processing, specify the workload, interfaces and available cabinet space.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.