DTL C
Electrical test & measurement

Current & voltage transducers
These flexible rope-style Rogowski coil current transformers convert AC operating current into a low-voltage AC millivolt signal for use with microprocessor-based circuits, such as power meters. Because the coil is flexible, it can be installed around large conductors or bundles of conductors where solid-core current transformers cannot fit.
The coil is placed around the conductor and outputs a signal proportional to the current flowing through it. Polarity is marked with an arrow, which must point towards the load, in the direction of current flow. The current input range is 5 to 5000 A AC, and calibrated ranges of 5–1200 A, 12.5–3000 A and 25–6000 A are available, with output sensitivities of 100 mV, 40 mV or 20 mV at 50 Hz.
Accuracy is ±0.5 % from 10 % to 120 % of rated current, with a temperature drift of ±0.07 %. The frequency range is 20 Hz to 5 kHz.
The coils are rated for overvoltage category CAT III 1000 V and CAT IV 600 V, with a dielectric strength of 7400 V AC at 50/60 Hz for one minute, and may be used at altitudes up to 3000 m. The housing is made of orange flame-retardant thermoplastic rubber to UL 94 V-0, and the coil diameter is 0.61 in. Connection is made with stripped and tinned 26 AWG lead wires to UL Style 20940. Operating temperature is 4 to 158 °F at 5 to 95 % RH non-condensing, and storage is permitted from −40 to 185 °F. CE, cULus and RoHS2 are listed.
The coils are available in several window sizes, RCT16, RCT24, RCT36 and RCT47, with article numbers such as 148147 to 148155. They are compatible with the KW350-P1-D-S-RC, KW320-P1-D-W-RC-XX, KW320-P1-D-W-RC-PC, KW1850-P1-D-W and KW1850-P1-D-S power meters.
Applications named for the current transformers are tenant billing, energy and demand metering, load surveys, LEED and green projects, power quality monitoring and harmonic monitoring. Please send the conductor size or bundle dimensions, the current range and the meter to which the coils will be connected with your enquiry.
148147, 148148, 148149, 148151, 148152, 148153, 148154, 148155, 148156, 148157
Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.