DTL C
Electrical test & measurement

Power quality analysers
The S711E-ROG is a three-phase power analyser for panel mounting, supplied as a kit together with three Rogowski coils. It is intended for measuring and storing the electrical parameters of three-phase systems and for analysing energy consumption and power quality, and is well suited to retrofitting existing switchboards and to energy audits.
The instrument measures voltage directly and current through the Rogowski inputs, and calculates active, reactive and apparent power and energy. Energy and power are measured bidirectionally in all four quadrants, total harmonic distortion is evaluated up to the 15th harmonic, and demand (DMD) values are calculated; a digital input can be used for demand synchronisation. Minimum, average and maximum values of active and reactive power are recorded in an 8 MB log memory, and real-time data is shown on a backlit 76 × 61 mm LCD.
The Rogowski inputs are scaled for 500, 4000 or 20000 A, and the maximum measurable voltage is 600 V AC line to line, with an input impedance above 1.3 MΩ and a frequency range of 45–65 Hz. Voltage accuracy is ±0.2 % of reading from 10 % of full scale, current accuracy ±0.4 % of reading from 5 % of full scale, and frequency accuracy 0.1 % of reading ±1 digit. Active power and energy correspond to class 0.5 and reactive power and energy to class 2 according to IEC/EN 61557-12.
Depending on the model, communication is via RS485 with Modbus RTU at 300 to 57600 bps, or via 10/100 Mbps Ethernet with HTTP, Modbus TCP, NTP and DHCP and a built-in web server. Digital outputs work in alarm mode with a reaction time of at most 1 s or as energy pulse outputs with a 50 ms pulse; AO models add an analogue output selectable for 0–20 or 4–20 mA with a maximum load of 500 Ω. RS485 models are supplied with 230 or 115 V AC, models with auxiliary supply accept 85–265 V AC or 110 V DC ±15 %.
The housing measures 96 × 96 × 39 mm, weighs at most 310 g and requires a 91 × 91 mm panel cut-out. Measuring terminals take 1.5 mm² wire, I/O, auxiliary, RS485 and Rogowski terminals 2.5 mm². Operating temperature is −25 to +55 °C and storage temperature −25 to +75 °C, at up to 80 % humidity without condensation. Installation in a switchboard with at least IP54 protection and an external 250 mA T-type fuse are recommended. The analyser carries CE marking and complies with RoHS, EN 61010-1, EN 61326-1 and IEC/EN 62053-21, -23 and -31.
Kits are available with 30 cm (Ø 9.5 cm), 45 cm (Ø 14 cm) or 70 cm (Ø 22 cm) coils, each with RS485 (S711EROGMOD30/45/70) or Ethernet (S711EROGETH30/45/70), and RS485 versions with an analogue output (…AO). Applications include energy management and building management systems, industrial power monitoring, energy consumption analysis and power quality analysis. Please state the conductor size, required coil length and preferred interface in your enquiry.
S711EROGMOD30, S711EROGMOD45, S711EROGMOD70, S711EROGETH30, S711EROGETH45, S711EROGETH70, S711E-ROG, S711EROGMOD30AO, S711EROGMOD45AO, S711EROGMOD70AO
Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.
For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.
For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.
Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.