DEIF A/S MTR-4
DEIF A/S

MTR-4 programmable multi-transducer for power networks

Current & voltage transducers

Manufacturer
DEIF A/S
Model
MTR-4
Instrument type
Current & voltage transducers
Measured values
voltage, current, frequency, power, power factor, THD, energy
Max. voltage
600 V L-N; 1000 V L-L
Max. current
12.5 A
Frequency range
16 to 400 Hz
Accuracy class, power
0.5 (0.4)
Accuracy class, energy
active class 1; reactive class 2
Analogue outputs
0 to 4, configurable
Relay outputs
2 (option)
Response time
< 50 ms (FAST analogue output)
Communication
RS-485 Modbus RTU; USB 2.0 for configuration
Auxiliary supply
48 to 276 V AC; 20 to 300 V DC
Protection
IP20
Mounting
DIN rail 35 × 15 mm
Dimensions
100 × 75 × 105.5 mm
Weight
370 g
Request a quote
Review enquiry

MTR-4 is a programmable multi-transducer that measures, analyses and monitors single-phase and three-phase electrical power networks. It converts the electrical quantities of a network into standard analogue signals and digital data for control systems, and it is designed for applications that require marine approval, such as ships and offshore platforms.

The transducer samples the voltage and current signals at high speed and calculates true RMS values, which also allows transient events to be acquired. A built-in microcontroller computes voltage, current, frequency, power, power factor, THD and energy. More than 50 parameters are available for assignment to the outputs.

The device accepts up to 600 V line-to-neutral and 1000 V line-to-line, and currents up to 12.5 A. The frequency measuring range is 16 to 400 Hz. The accuracy class for power is 0.5 (0.4); energy is measured to class 1 for active and class 2 for reactive energy. With the FAST analogue output option the response time is below 50 ms.

Up to four analogue outputs can be configured, and versions with two relay outputs are available. Communication is via RS-485 with Modbus RTU, and a USB 2.0 interface is used for configuration. A universal auxiliary supply accepts 48 to 276 V AC or 20 to 300 V DC.

The housing is designed for DIN rail mounting on a 35 × 15 mm rail and has IP20 protection. It measures 100 × 75 × 105.5 mm and weighs 370 g. The device is built to EN 61010-1 and EN 60688 and tested to EN 61000-6-2/-4 and to the environmental tests of EN 60068-2-1, -2, -6, -27 and -30.

Versions are identified by the number of analogue outputs: MTR-4-015 without analogue output, MTR-4-105, -215, -315 and -415 with one to four analogue outputs, and variants with two relay outputs and one analogue output, including a tropicalised version.

Listed applications are power generation, marine and offshore installations, wind turbine retrofitting, grid connection, hybrid power systems, data centres, hospitals and telecom. Please tell us the network type, voltage and current ranges and the number and type of outputs needed.

Part numbers · 12

1200510020, 1200510021, 1200510022, 1200510023, 1200510024, 2962390110.01, 2962390110.02, 2962390110.03, 2962390110.04, 2962390110.05, 2962390110.09, 2962390110.11

Industry applications

Selection notes

Match the instrument to the circuit and measurement category. Include the wiring arrangement and ratios of any external current or voltage transformers.

For an installed instrument, copy the complete ordering code and its suffixes from the nameplate. Identify the part that will remain in service and the part that needs to be replaced. A photograph of the connection face or terminal markings helps resolve differences between versions that share the same housing.

For a new installation, describe what the instrument must measure or control and where the reading will be used. Give the normal operating conditions separately from short peaks. Include units with every numerical value. A drawing with the available space, orientation and access for removal gives the supplier a practical starting point.

Add the quantity for each position and identify any accessories that belong with it. Where a particular drawing, material certificate or calibration record is required, mention it with the line item. Submit the list with the destination country so that the response can cover the requested configuration and delivery.